• Link to X
  • Link to LinkedIn
  • Link to Mail
  • ABOUT UI
    • Business Partners
    • Careers
    • Contact Us
    • News & Press
    • Our Team
    • Press Releases
    • Branding Guidelines
  • CONTACT
Uptime Institute Blog
  • Journal
    • Journal Home
    • Executive
    • Operations
    • Design
  • AI Services
    • AI Infrastructure Advisory
  • Tier Certification
    • Overview
    • Design
    • Construction
    • Operations
    • Tier Gap Analysis
    • Prefabricated/Modular
    • Tier Certifications List
  • Professional Services
    • Overview
    • Infrastructure Services
    • Management and Operations Services
    • Energy and Sustainability Services
    • Consulting Services
  • Education
    • Education Framework
    • Course Calendar
    • Competency & Confidence Assessments
    • Private Education
    • Graduate Roster
  • Events
    • Industry Events
    • Leadership Events
    • Network Events
  • Network
    • Overview
    • Network Calendar
    • Network Roster
    • Request Corporate Access
    • Request Guest Access
    • Uptime Network Portal
  • Intelligence
  • Clients
    • Client Stories
  • Resources
    • Data Center Industry Surveys
    • Ebooks
    • Journal Blog
    • Product Datasheets
    • Research & Reports
    • Tier Specification Documents
    • Tools
    • Webinars
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu
Blog - Latest News
2020

Are IT Infrastructure Outages Getting Longer?

March 30, 2020/in Executive, Operations/by Andy Lawrence, Executive Director of Research, Uptime Institute, [email protected]

One of the findings of Uptime Institute’s recently published report Annual outage analysis 2020 is that the most serious categories of outages — those that cause a significant disruption in services — are becoming more severe and more costly. This isn’t entirely surprising: individuals and businesses alike are becoming ever more dependent on IT, and it is becoming harder to replicate or replace an IT service with a manual system.

But one of the findings raises both red flags and questions: Setting aside those that were partial and incidental (which had minimal impact), publicly reported outages over the past three years appear to be getting longer. And this, in turn, is likely to be one of the reasons why the costs and severity of outages have been rising.

The table above shows the numbers of publicly reported outages collected by Uptime Institute in the years 2017-2019, except for those that did not have a financial or customer impact or those for which there was no known cause. The figures show outages are on the rise. This is due to a number of factors, including greater deployment of IT services and better reporting. But they also show a tilt in the data towards longer outages — especially those that lasted more than 48 hours. (This is true even though one of the biggest causes of lengthy outages — ransomware — was excluded from our sample.)

The outage times reported are until full IT service recovery, not business recovery — it may take longer, for example, to move aircraft back to where they are supposed to be, or to deal with backlogs in insurance claims. This trend is not dramatic, but it is real and it is concerning, because a 48-hour interruption can be lethal for many organizations.

Why is it happening? Complexity and interdependency of IT systems and greater dependency on software and data are very likely to be big reasons. For example, Uptime’s Institute’s research shows that fewer big outages are caused by power failure in the data center and more by IT systems configuration now than in the past. While resolving facility engineering issues may not be easy, it is usually a relatively predictable matter: failures are often binary, and very often recovery processes have been drilled into the operators and spare parts are kept at hand. Software, data integrity and damaged/interrupted cross-organizational business processes, however, can be much more difficult issues to resolve or sometimes even to diagnose — and these types of failure are becoming much more common (and yes, sometimes they are triggered by a power failure). Furthermore, because failures can be partial, files may become out of sync or even be corrupted.

There are lessons to be drawn. The biggest is that the resiliency regimes that facilities staff have lived by for three decades or more need to be extended and integrated into IT and DevOps and fully supported and invested in by management. Another is that while disaster recovery may be slowly disappearing as a type of commercial backup service, the principles of vigilance, recovery, and fail over – especially when under stress – are more important than ever.


The full report Annual outage analysis 2020 is available to members of the Uptime Institute Network which can be requested here.

Share this:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on LinkedIn (Opens in new window) LinkedIn
  • Share on Reddit (Opens in new window) Reddit
  • Share on WhatsApp (Opens in new window) WhatsApp
  • Email a link to a friend (Opens in new window) Email
Tags: Data Center, data center failures, IT Outages
https://journal.uptimeinstitute.com/wp-content/uploads/2020/02/GettyImages-1202490579-blog.jpg 1000 2700 Andy Lawrence, Executive Director of Research, Uptime Institute, [email protected] https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, [email protected]2020-03-30 06:00:592025-10-30 15:14:44Are IT Infrastructure Outages Getting Longer?
You might also like
Investments back two-phase cooling as water cold plate successor Investments back two-phase cooling as water cold plate successor
Data Center AI Creates New RisksGetty Data Center AI (Artificial Intelligence) Creates New Risks
Lithium-Ion Batteries in the Data Center2019 Lithium Ion Batteries for the data center. Are they ready for production yet?
Colocation and public cloud growth masks enterprise expansion Colocation and public cloud growth masks enterprise expansion
The shock waves from Ukraine The shock waves from Ukraine
Does the spread of direct liquid cooling make PUE less relevant? Does the spread of direct liquid cooling make PUE less relevant?
Are data centers to blame for power quality issues? Are data centers to blame for power quality issues?
IT-agnostic DLC systems: key considerations IT-agnostic DLC systems: key considerations

Content Categories

  • Journal Home
  • Executive
  • Operations
  • Design

Subscribe to Journal via Email

Enter your email address to subscribe to Uptime Institute Journal and receive notifications of new articles by email.

  • Recent

Tags

Accredited Tier Designer (9) AI (24) artificial intelligence (19) ATD (10) Carbon Emissions (7) Climate Change (13) Cloud (23) Cloud Computing (17) Cloud Costs (15) Cloud Infrastructure (29) Cloud Migration (8) Colocation (7) cooling (13) Data Center (261) Data Center Availability (40) Data Center Cooling (13) Data Center Design (45) Data Center Disaster Recovery (7) Data Center Energy Efficiency (34) Data Center Facilities Management (43) Data Center Operations (67) data center power (9) Data Center Staffing (19) DCIM (9) digital Infrastructure (126) energy (8) Energy Efficiency (38) Environmental Sustainability (18) IT (7) IT Efficiency (17) IT Outages (10) M&O (6) outages (12) Public Cloud (7) PUE (10) Regulations (25) Resiliency (9) security (7) Sustainability (34) Sustainability Reporting (7) Tier Certification (26) Tier Certification Constructed Facility (16) Uptime Institute FORCSS (6) Uptime Institute Network (13) Uptime Institute Symposium (6)
© 2014-2025 Uptime Institute, LLC All rights reserved.
  • Link to X
  • Link to LinkedIn
  • Link to Mail
Link to: COVID-19: IT organizations move from planning to implementation Link to: COVID-19: IT organizations move from planning to implementation COVID-19: IT organizations move from planning to implementationData Center & IT Service Delivery Operations During COVID-19 20202020 Link to: COVID-19: Q&A (Part 1): Staff Management Link to: COVID-19: Q&A (Part 1): Staff Management COVID19: Digital Infrastructure Q&ACOVID-19: Q&A (Part 1): Staff Management
Scroll to top Scroll to top Scroll to top