• Link to X
  • Link to LinkedIn
  • Link to Mail
  • ABOUT UI
    • Business Partners
    • Careers
    • Contact Us
    • News & Press
    • Our Team
    • Press Releases
    • Branding Guidelines
  • CONTACT
Uptime Institute Blog
  • Journal
    • Journal Home
    • Executive
    • Operations
    • Design
  • AI Services
    • AI Infrastructure Advisory
  • Tier Certification
    • Overview
    • Design
    • Construction
    • Operations
    • Tier Gap Analysis
    • Prefabricated/Modular
    • Tier Certifications List
  • Professional Services
    • Overview
    • Infrastructure Services
    • Management and Operations Services
    • Energy and Sustainability Services
    • Consulting Services
  • Education
    • Education Framework
    • Course Calendar
    • Competency & Confidence Assessments
    • Private Education
    • Graduate Roster
  • Events
    • Industry Events
    • Leadership Events
    • Network Events
  • Network
    • Overview
    • Network Calendar
    • Network Roster
    • Request Corporate Access
    • Request Guest Access
    • Uptime Network Portal
  • Intelligence
  • Clients
    • Client Stories
  • Resources
    • Data Center Industry Surveys
    • Ebooks
    • Journal Blog
    • Product Datasheets
    • Research & Reports
    • Tier Specification Documents
    • Tools
    • Webinars
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu
Blog - Latest News
The weakest link dictates cloud outage compensation

The weakest link dictates cloud outage compensation

June 1, 2022/in Executive, Operations/by Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, [email protected]

Cloud providers offer services that are assembled by users into applications. An outage of any single cloud service can render an application unavailable. Importantly, cloud providers guarantee the availability of individual services, not of entire applications. Even if a whole application becomes unresponsive due to a provider outage, compensation is only due for the individual services that failed.

A small outage on a tiny part of an application may wreak havoc with an application (and even an entire business), but the provider will only award compensation for the weakest link that caused the outage.

A service level agreement (SLA) sets out the likely or promised availability of a specific cloud service, plus compensation due to the user if the provider fails to meet this availability. There is a different SLA for each cloud service.

Consider the cloud architecture in Figure 1, which shows traffic flows between virtual machines and a virtual load balancer. The load balancer distributes traffic across nine virtual machines. The virtual machines use the infrastructure as a service (IaaS) model, meaning the user is responsible for architecting virtual machines to be resilient. The load balancer, however, is a platform as a service (PaaS), which should mean the provider has architected it for resiliency. (More information on cloud models can be found in Uptime Institute’s recent report Cloud scalability and resiliency from first principles.)

Diagram: Simple load-balanced cloud architecture
Figure 1 Simple load-balanced cloud architecture

If the load balancer becomes unresponsive, the entire application is unusable as traffic can’t be routed to the virtual machines. The load balancer in this architecture is the weakest link.

The provider is responsible for the resiliency of the load balancer. Is the load balancer a single point of failure? It depends on the perception of the user. It may not be regarded as a single point of failure if the user is fully confident the provider has architected resiliency correctly through, for example, redundant servers or automatic failover. If the user is less convinced, they may consider the load balancer as a single point of failure because it is controlled by a single entity over which the user has limited visibility and control.

The virtual machines are still “available” because they are still in operation and can be accessed by the user for administration or maintenance — they just can’t be accessed by the end user via the application. The load balancer is the problem, not the virtual machines. In this scenario, no compensation is payable for the virtual machines even though the application has gone down.

To understand the financial impact, we’ll assume each virtual machine and load balancer costs $3 per month. As an example of a cloud SLA, Microsoft Azure offers compensation of 10% of the monthly cost of the load balancer if it fails to be available for 99.99% to 99.9% of a month. Similar terms also apply to virtual machines.

If the load balancer is down for 43 minutes, then Microsoft Azure is obliged to pay 10% of the monthly fee of the load balancer, so $0.30 in this case. It is not obliged to pay for the virtual machines as these continued in operation, despite the application becoming unresponsive. The total monthly cost of the application is $30, and the compensation is $0.30, which means the payment for the outage is 1% of the monthly fee paid to Microsoft Azure — a paltry sum compared with the likely impact of the outage. Table 1 provides an overview of the refunds due in this scenario.

Table: SLA refunds due in example scenario
Table 1 SLA refunds due in example scenario

This example demonstrates two points. First, cloud providers provide services that users use to build applications. Their responsibility ends with these services. The analogy of cloud services as toy bricks may seem trite, but it conveys effectively some fundamental aspects of the cloud model. A toy company may guarantee the quality of its bricks, but it would not guarantee the quality of a model completed by an enthusiastic builder, no matter how well built.

In the architecture in Figure 1, for example, the user could have designed a more scalable application. They could have reduced the cost of virtual machines by implementing autoscaling, which would automatically terminate the unutilized virtual machines when not in use (such as when the load balancer went down). The user is ultimately responsible for building a resilient and scalable application, just as the quality of the toy model is the builder’s responsibility.

Second, this example also demonstrates that an SLA is not an insurance policy. It does not mitigate the business impact of downtime. In practice, compensation for cloud outages is likely to be less than originally assumed by users due to nuances in contract terms, which reduce the provider’s liability. Cloud customers must identify single points of failure in their applications and assess the risk and impact of an outage of these services. An outage of these services can render an application unavailable, but SLA compensation is unlikely to even cover the cost of the cloud services, let alone business losses. Ultimately, users are responsible for architecting greater resiliency in their applications to reduce the impact of outages.

Share this:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on LinkedIn (Opens in new window) LinkedIn
  • Share on Reddit (Opens in new window) Reddit
  • Share on WhatsApp (Opens in new window) WhatsApp
  • Email a link to a friend (Opens in new window) Email
Tags: Cloud Computing, Cloud Infrastructure, Cloud Outages, Cloud SLAs, Data Center, digital Infrastructure, IaaS
https://journal.uptimeinstitute.com/wp-content/uploads/2022/05/Weakest-Link-featured.jpg 628 1200 Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, [email protected] https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, [email protected]2022-06-01 07:00:002022-05-17 16:57:39The weakest link dictates cloud outage compensation
You might also like
Cloud a viable choice amidst uncertain AI returns Cloud a viable choice amidst uncertain AI returns
Project approval will hinge on local benefit guarantees Project approval will hinge on local benefit guarantees
Is Google a credible enterprise cloud? Is Google a credible enterprise cloud?
Data Center Outages, Incidents, and Industry Transparency
The shock waves from Ukraine The shock waves from Ukraine
Neoclouds: a cost-effective AI infrastructure alternative Neoclouds: a cost-effective AI infrastructure alternative
UI 2020 Five Trends for 2021: accountability, automation, edge, sustainability, innovation
24x7 carbon-free energy (part two): getting to 100% 24×7 carbon-free energy (part two): getting to 100%

Content Categories

  • Journal Home
  • Executive
  • Operations
  • Design

Subscribe to Journal via Email

Enter your email address to subscribe to Uptime Institute Journal and receive notifications of new articles by email.

  • Recent

Tags

Accredited Tier Designer (9) AI (24) artificial intelligence (19) ATD (10) Carbon Emissions (7) Climate Change (13) Cloud (23) Cloud Computing (17) Cloud Costs (15) Cloud Infrastructure (29) Cloud Migration (8) Colocation (7) cooling (13) Data Center (261) Data Center Availability (40) Data Center Cooling (13) Data Center Design (45) Data Center Disaster Recovery (7) Data Center Energy Efficiency (34) Data Center Facilities Management (43) Data Center Operations (67) data center power (9) Data Center Staffing (19) DCIM (9) digital Infrastructure (126) energy (8) Energy Efficiency (38) Environmental Sustainability (18) IT (7) IT Efficiency (17) IT Outages (10) M&O (6) outages (12) Public Cloud (7) PUE (10) Regulations (25) Resiliency (9) security (7) Sustainability (34) Sustainability Reporting (7) Tier Certification (26) Tier Certification Constructed Facility (16) Uptime Institute FORCSS (6) Uptime Institute Network (13) Uptime Institute Symposium (6)
© 2014-2025 Uptime Institute, LLC All rights reserved.
  • Link to X
  • Link to LinkedIn
  • Link to Mail
Link to: The shock waves from Ukraine Link to: The shock waves from Ukraine The shock waves from UkraineThe shock waves from Ukraine Link to: Outages: understanding the human factor Link to: Outages: understanding the human factor Outages: understanding the human factorOutages: understanding the human factor
Scroll to top Scroll to top Scroll to top