• Link to X
  • Link to LinkedIn
  • Link to Mail
  • ABOUT UI
    • Business Partners
    • Careers
    • Contact Us
    • News & Press
    • Our Team
    • Press Releases
    • Branding Guidelines
  • CONTACT
Uptime Institute Blog
  • Journal
    • Journal Home
    • Executive
    • Operations
    • Design
  • AI Services
    • AI Infrastructure Advisory
  • Tier Certification
    • Overview
    • Design
    • Construction
    • Operations
    • Tier Gap Analysis
    • Prefabricated/Modular
    • Tier Certifications List
  • Professional Services
    • Overview
    • Infrastructure Services
    • Management and Operations Services
    • Energy and Sustainability Services
    • Consulting Services
  • Education
    • Education Framework
    • Course Calendar
    • Competency & Confidence Assessments
    • Private Education
    • Graduate Roster
  • Events
    • Industry Events
    • Leadership Events
    • Network Events
  • Network
    • Overview
    • Network Calendar
    • Network Roster
    • Request Corporate Access
    • Request Guest Access
    • Uptime Network Portal
  • Intelligence
  • Clients
    • Client Stories
  • Resources
    • Data Center Industry Surveys
    • Ebooks
    • Journal Blog
    • Product Datasheets
    • Research & Reports
    • Tier Specification Documents
    • Tools
    • Webinars
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu
Blog - Latest News
The two sides of a sustainability strategy

The two sides of a sustainability strategy

August 22, 2025/in Executive, Operations/by Jay Dietrich, Research Director of Sustainability, Uptime Institute, [email protected]

While much has been written, said and taught about data center sustainability, there is still limited consensus on the definition and scope of an ideal data center sustainability strategy. This lack of clarity has created much confusion, encouraged many operators to pursue strategies with limited results, and enabled some to make claims that are ultimately of little worth.

To date, the data center industry has adopted three broad, complementary approaches to sustainability:

  • Facility and IT sustainability. This approach prioritizes operational efficiency, minimizing the energy, direct carbon and water footprints of IT and facility infrastructure. It directly addresses the operational impacts of individual facilities, reducing material and energy use and costs. Maximizing the sustainability of individual facilities is key to addressing the increased government focus on regulating individual data centers.
  • Ecosystem sustainability. This strategy focuses on carbon neutrality (or carbon negativity), water positivity and nature positivity across the enterprise. Ecosystem sustainability offsets the environmental impacts of an enterprise’s operations, which may increase business costs.
  • Overall sustainability. While some data center operators promote the sustainability of their facilities with limited efforts on ecosystem sustainability, others build their brand around ecosystem sustainability with minimal discussion about the sustainability of their facilities. Although it is common for organizations to make efforts in both areas, it is less common for the strategies to be integrated as a part of a coherent plan.

Each approach has its own benefits and challenges, providing different levels of business and environmental performance improvement. This report is an extension and update to the Sustainability Series of reports, published by Uptime Intelligence in 2022 (see below for a list of the reports), which detailed the seven elements of a sustainability strategy.

Data center sustainability

Data center sustainability involves incorporating sustainability and efficiency considerations into siting, design and operational processes throughout a facility’s life. The organizations responsible for siting and design, IT operations, facility operations, procurement, contracting (colocation and cloud operators) and waste management must embrace the enterprise’s overall sustainability strategy and incorporate it into their daily operations.

Achieving sustainability objectives may require a more costly initial investment for an individual facility, but the reward is likely an overall lower cost of ownership over its life. To implement a sustainability strategy effectively, an operator must address the full range of sustainability elements:

  • Siting and design. Customer and business needs dictate a data center’s location. Typically, multiple sites will satisfy these criteria, however, the location should also be selected based on whether it can help optimize the facility’s sustainability performance. Operators should focus on maximizing free cooling and carbon-free energy consumption while minimizing energy and water consumption. The design should choose equipment and materials that maximize the facility’s environmental performance.
  • Cooling system. The design should minimize water and energy use, including capturing available free-cooling hours. In water-scarce or water-stressed regions, operators should deploy waterless cooling systems. Where feasible and economically viable, heat reuse systems should also be incorporated into the design.
  • Standby power system. The standby power system design should enable fuel flexibility (able to use low-carbon or carbon-free fuels) and provide primary power capability. It should be capable and permitted to deliver primary power for extended periods. This enables the system to support grid reliability and assist in addressing the intermittency of wind and solar generation contracted to supply power to the data center, thereby reducing the carbon intensity of the electricity consumption.
  • IT infrastructure efficiency. IT equipment should be selected to maximize the average work delivered per watt of installed capacity. The installed equipment should run at or close to the highest practical utilization level of the installed workloads while meeting their reliability and resiliency requirements. IT workload placement and management software should be used to monitor and optimize the IT infrastructure performance.
  • Carbon–free energy consumption. Operators should work with electricity utilities, energy retailers, energy developers and regulators to maximize the quantity of clean energy consumed and minimize location-based emissions. Over time, they should plan to increase carbon-free energy consumption to 90% or more of the total consumption. Timelines will vary by region depending on the economics and availability of carbon-free energy.
  • End-of-life equipment reuse and materials recovery. Operators need an end-of-life equipment management process that maximizes the reuse of equipment and components, both within the organization and through refurbishment and use by others. Where equipment must be scrapped, there should be a process in place to recover valuable metals and minerals, as well as energy, through environmentally responsible processes.  
  • Scope 3 emissions management. Operators should require key suppliers to maintain a sustainability strategy, publicly disclose their greenhouse gas (GHG) emissions inventory and reduction goals, and demonstrate progress toward their sustainability objectives. There should be consequences in place for suppliers that fail to show reasonable progress.

While these strategies may appear simple, creating and executing a sustainability strategy requires the commitment of the whole organization — from technicians and engineers to procurement, finance and executive leadership. In some cases, financial criteria may need to shift from considering the initial upfront costs to the total cost of ownership and the revenue benefits/enhancements gained from a demonstrably sustainable operation. A data center sustainability strategy can enhance business and environmental performance.

Ecosystem sustainability

An ecosystem sustainability strategy emphasizes mitigating and offsetting the environmental impacts of an operator’s data center portfolio. While these efforts do not change the environmental operating profile of individual data centers, they are designed to benefit the surrounding community and natural environment. Such projects and environmental offsets are typically managed at the enterprise level rather than the facility level and represent a cost to the enterprise.

  • Carbon-neutral or carbon-negative operations. Operators should purchase energy attribute certificates (EACs) and carbon capture offsets to reduce or eliminate their Scope 1, 2 and 3 emissions inventory. The offsets are generated primarily from facilities geographically separate from the data center facilities. EACs and offsets can be purchased directly from brokers or from operators of carbon-free energy or carbon capture systems.
  • Water-positive operations. Operators should work with communities and conservation groups to implement water recharge and conservation projects that return more water to the ecosystem than is used across their data centers. Examples include wetlands reclamation, water replenishment, support of sustainable agriculture, and leak detection and minimization systems for water distribution networks. These projects can benefit the local watershed or unrelated, geographically distinct watersheds.
  • Nature-positive facilities. The data center or campus should be landscaped to regenerate and integrate with the natural landscape and local ecosystem. Rainwater and stormwater should be naturally filtered and reused where practical. The landscape should be designed and managed to support local flora and fauna, ensuring that the overall campus is seamlessly integrated into the local ecosystem. The overall intent is to make the facility as “invisible” as possible to the local community.
  • Emissions reductions achieved with IT tools. Some operators and data center industry groups quantify and promote the emissions reduction benefits (known as Scope 4 “avoided emissions”) generated from the operation of the IT infrastructure. They assert that the “avoided emissions” achieved through the application of IT systems to increase the operational efficiency of systems or processes, or “dematerialize” products, can offset some or all of the data center infrastructure’s emissions footprint. However, these claims should be approached with caution, as there is a high degree of uncertainty in the calculated quantities of “avoided emissions.”
  • Pro-active work with supply chains. Some operators work directly with supply chain partners to decarbonize their operations. This approach is practical when an enterprise represents a significant percentage of a supplier’s revenue. However, it becomes impractical when an operator’s purchases represent only a small percentage of the supplier’s business.

Ecosystem sustainability seeks to deliver environmental performance improvements to operations and ecosystems outside the operator’s direct control. These improvements compensate for and offset any remaining environmental impacts following the full execution of the data center sustainability strategy. They typically represent a business cost and enhance an operator’s commercial reputation and brand.

Where to focus

Facility and IT and ecosystem sustainability strategies are complementary, addressing the full range of sustainability activities and opportunities. In most organizations, it will be necessary to cover all of these areas, often by different teams focusing on their respective domains.

An operator’s primary focus should be improving the operational efficiency and sustainability performance of its data centers. Investments in the increased use of free cooling, automated control of chiller and IT space cooling systems, and IT consolidation projects can yield significant energy, water and cost savings, along with reductions in GHG emissions. These improvements will not only reduce the environmental footprint of the data center but can also improve its business performance.

These efforts also enable operators to proactively address emerging regulatory and standards frameworks. Such regulations are intended to increase the reporting of operating data and metrics and may ultimately dictate minimum performance standards for data centers.

To reduce the Scope 2 emissions (purchased electricity) associated with data center operations to zero, operators need to work with utilities, energy retailers, and the electricity transmission and distribution system operators. The shared goal is to help build a resilient, interconnected electricity grid populated by carbon-free electricity generation and storage systems — a requirement for government net-zero mandates.

Addressing ecosystem sustainability opportunities is a valuable next step in an operator’s sustainability journey. Ecosystem projects can enhance the natural environment surrounding the data facility, improve the availability of carbon-free energy and water resources locally and globally, and directly support, inform and incentivize the sustainability efforts of customers and suppliers.

Data center sustainability should be approached in two separate ways: first, the infrastructure itself and, second, the ecosystem. Confusion and overlap between these two aspects can lead to unfortunate results. For example, in many cases, a net-zero and water-positive data center program is (wrongly) accepted as an indication that an enterprise is operating a sustainable data center infrastructure.


The Uptime Intelligence View

Operators should prioritize IT and facilities sustainability over ecosystem sustainability. The execution and results of an IT and facilities sustainability strategy directly minimize the environmental footprint of a data center portfolio, while maximizing its business and sustainability performance.

Data reporting and minimum performance standards embodied in enacted or proposed regulations are focused on the operation of the individual data centers, not the aggregated enterprise-level sustainability performance. An operator must demonstrate that they have a highly utilized IT infrastructure (maximized work delivered per unit of energy consumed) and minimized the energy and water consumption and GHG emissions associated with its facility operations.

Pursuing an Ecosystem sustainability strategy is the logical next step for operators that want to do more and further enhance their sustainability credentials. However, an ecosystem sustainability strategy should not be pursued at the expense of an IT and Facilities strategy to shield poor or marginal facility and IT systems performance.

The following Uptime Institute expert was consulted for this report:
Jay Paidipati, Vice President Sustainability Program Management, Uptime Institute

Other related reports published by Uptime Institute include:
Creating a sustainability strategy
IT Efficiency: the critical core of sustainability
Three key elements: water, circularity and siting
Navigating regulations and standards
Tackling greenhouse gases
Reducing the energy footprint

Share this:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on LinkedIn (Opens in new window) LinkedIn
  • Share on Reddit (Opens in new window) Reddit
  • Share on WhatsApp (Opens in new window) WhatsApp
  • Email a link to a friend (Opens in new window) Email
Tags: Data Center, digital Infrastructure, IT Efficiency, Sustainability
https://journal.uptimeinstitute.com/wp-content/uploads/2025/08/The-two-sides-of-a-sustainability-strategy-featured.jpg 540 1030 Jay Dietrich, Research Director of Sustainability, Uptime Institute, [email protected] https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jay Dietrich, Research Director of Sustainability, Uptime Institute, [email protected]2025-08-22 15:00:002025-08-22 10:01:09The two sides of a sustainability strategy
You might also like
Building trust: working with AI-based tools Building trust: working with AI-based tools
Data center operators will face more grid disturbances Data center operators will face more grid disturbances
UI 2021 Network problems causing ever more outages
Why are governments investigating cloud competitiveness? Why are governments investigating cloud competitiveness?
Mark Thiele from Switch examines the options in today’s data center industry
AI in data: sorting reality from hallucination
IT efficiency: an untapped power resource IT efficiency: an untapped power resource
2020 Are IT Infrastructure Outages Getting Longer?

Content Categories

  • Journal Home
  • Executive
  • Operations
  • Design

Subscribe to Journal via Email

Enter your email address to subscribe to Uptime Institute Journal and receive notifications of new articles by email.

  • Recent

Tags

Accredited Tier Designer (9) AI (24) artificial intelligence (19) ATD (10) Carbon Emissions (7) Climate Change (13) Cloud (23) Cloud Computing (17) Cloud Costs (15) Cloud Infrastructure (29) Cloud Migration (8) Colocation (7) cooling (13) Data Center (261) Data Center Availability (40) Data Center Cooling (13) Data Center Design (45) Data Center Disaster Recovery (7) Data Center Energy Efficiency (34) Data Center Facilities Management (43) Data Center Operations (67) data center power (9) Data Center Staffing (19) DCIM (9) digital Infrastructure (126) energy (8) Energy Efficiency (38) Environmental Sustainability (18) IT (7) IT Efficiency (17) IT Outages (10) M&O (6) outages (12) Public Cloud (7) PUE (10) Regulations (25) Resiliency (9) security (7) Sustainability (34) Sustainability Reporting (7) Tier Certification (26) Tier Certification Constructed Facility (16) Uptime Institute FORCSS (6) Uptime Institute Network (13) Uptime Institute Symposium (6)
© 2014-2025 Uptime Institute, LLC All rights reserved.
  • Link to X
  • Link to LinkedIn
  • Link to Mail
Link to: ‘Reasoning’ will increase the infrastructure footprint of AI Link to: ‘Reasoning’ will increase the infrastructure footprint of AI ‘Reasoning’ will increase the infrastructure footprint of AI‘Reasoning’ will increase the infrastructure footprint of AI Link to: Self-contained liquid cooling: the low-friction option Link to: Self-contained liquid cooling: the low-friction option Self-contained liquid cooling: the low-friction optionSelf-contained liquid cooling: the low-friction option
Scroll to top Scroll to top Scroll to top