• Link to X
  • Link to LinkedIn
  • Link to Mail
  • ABOUT UI
    • Business Partners
    • Careers
    • Contact Us
    • News & Press
    • Our Team
    • Press Releases
    • Branding Guidelines
  • CONTACT
Uptime Institute Blog
  • Journal
    • Journal Home
    • Executive
    • Operations
    • Design
  • AI Services
    • AI Infrastructure Advisory
  • Tier Certification
    • Overview
    • Design
    • Construction
    • Operations
    • Tier Gap Analysis
    • Prefabricated/Modular
    • Tier Certifications List
  • Professional Services
    • Overview
    • Infrastructure Services
    • Management and Operations Services
    • Energy and Sustainability Services
    • Consulting Services
  • Education
    • Education Framework
    • Course Calendar
    • Competency & Confidence Assessments
    • Private Education
    • Graduate Roster
  • Events
    • Industry Events
    • Leadership Events
    • Network Events
  • Network
    • Overview
    • Network Calendar
    • Network Roster
    • Request Corporate Access
    • Request Guest Access
    • Uptime Network Portal
  • Intelligence
  • Clients
    • Client Stories
  • Resources
    • Data Center Industry Surveys
    • Ebooks
    • Journal Blog
    • Product Datasheets
    • Research & Reports
    • Tier Specification Documents
    • Tools
    • Webinars
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu
Blog - Latest News

“Think Globally, Act Locally”: Re-Evaluating Data Center Resiliency in the Face of Climate Change

January 16, 2019/in Design, Executive, Operations/by Kevin Heslin

The 1970s-era environmental phrase “Think globally, act locally,” is an apt way for data center operators to consider the best approach to understand and address the effects of climate change on their facilities and IT operations TODAY.

Globally, we all hear that climate change threatens to bring warmer temperatures, stronger storms, rising sea levels, and more rain. It’s not too much of a stretch to agree that at the local level, this can mean increased flooding and droughts associated with higher ambient temperatures and winds, stronger lightning, and more humidity. So it’s not hard to understand that these changes are already posing significant implications for public infrastructures and real estate ventures, as well as their digital constituents including the delivery of IT services.

Uptime Institute advises data center operators and owners to evaluate their facilities and procedures considering the growing threat, and where possible, act to mitigate the risk from these environmental changes which will potentially impact their physical infrastructure along with their operational best practices currently in place.

Survey Results Show the Data Center Industry is Taking Action

In our 2018 survey of hundreds of data center owners and operators, we asked about climate change and what was being done to address it in their infrastructure and planning processes. Here’s what we saw:

Owners & Operators Should Refresh Plans Based on Latest Weather and Storm Models

To get started, data center operators should strive to create a baseline of service resiliency with climate change in mind. Many facilities have been designed to meet the level of flooding, storm, drought, or fire events as they were understood years ago. These facilities also may have adequate capacity to meet some amount of increased cooling demands from higher ambient temperatures, but the specific additional capacity may not be well understood relative to the needs brought about through climate change.

Resiliency assessments could reveal greater-than-expected vulnerabilities. For example, the operator of a 20-year-old data center originally built to withstand a 100-year storm as defined in the year 2000 may no longer withstand the greater flooding predicted to occur as part of a 100-year storm defined in 2020. For example, in Houston, TX, 19.5 inches of rain defined a 100-year storm as recently as 2000. Today, that same amount of rainfall is a 17.5-year event. By 2100, it is expected to be a 5.5-year event. As a corollary, 100-year events in the near future will involve far greater rainfall and flooding than we expect today. This evolving threat means that data centers slowly become less resilient and then suddenly are vulnerable, if planning and mitigation are not part of an ongoing planned process.

Hosting Providers Being Proactive, but Still Vulnerable to Underlying Risks

There are no shortcuts to these investigations. Moving to a hosting facility, does not necessarily lower an organization’s risk. Hosting facilities can also be just as vulnerable to a wide range of climate change impacts, and these providers must be subject to due diligence before hosting contracts are signed, just as in any other site evaluation process. And the questions which are part of due diligence should be more forward looking with climate change level stress provisions identified.

According to Uptime Institute’s 2018 survey, many hosting providers are taking climate change very seriously. The survey found that hosting providers are far more likely than any other vertical to have considered or taken a variety of climate change precautions than any other sector. As the chart below indicates, hosting providers (81%) were far more likely to say they were preparing for climate change than any other sector (industry average, 45%). They were also far more willing to re-evaluate technology selection.

Colocation (%) Telecommunications (%) Financial (%) Software/Cloud Services (%) Industry Average (%)
Preparing for Climate Change 81 60 61 57 45
Willingness to Re-Evaluate Technology Selection 54 33 33 32 33

Data center operators have many other operational issues to consider as well. Hardening the physical facility infrastructure is a good first step, but data center operators must also re-examine their MOPs, SOPs, and EOPs, as well as their supporting vendors’ SLAs.

One good example of proper planning is when a major brokerage in New York City, during Superstorm Sandy, remained 100% operational because it had developed and followed suitable procedures and best practices for addressing conditions proactively. Uptime Institute found that many firms like this that switched to generator power in advance of an expected utility outage remained operational through the storm and continued to successfully operate if supply procedures were in place to guarantee on-going fuel availability. In addition, these firms provided provisions for local operational staff whose homes and families were threatened by the storm.

Preparation Requires Careful Evaluation of Partners as well as Local Infrastructure

But data centers do not work as islands. A data center encircled by water, even if operational, cannot support the business if it loses local network connectivity. Likewise, flooded roadways and tunnels can interrupt fuel oil deliveries and block staff access. The extent of these threats cannot be fully evaluated without including an extensive list of local conditions ranging from town and village highway closure reports to statewide emergency services response plans as well as those plans from all telecommunications providers and other utilities. These services each have their own disaster recovery plans.

The incremental nature of climate change means that resiliency assessments cannot be one-time events. Data center resiliency in the face of climate change must be re-assessed often enough to keep pace with changing weather patterns, updated local and state disaster planning, and telecommunications and local infrastructure.

Costs Expected to Rise as Resources Become More Scare and Risks Increase

Finally, data center operators must keep abreast of a laundry list of costs expected to rise as a result of climate change. For example, insurance companies have already begun to increase premiums because of unexpected losses due to unprecedented and anomalous events. In the same way, resources such as water are expected to be increasingly expensive because of shortages and local restrictions. Utilities and suppliers could also be affected by these rising costs, which are likely to cause the prices of diesel fuel and electricity to increase.

Now is the time to evaluate climate change threats on a local basis, facility by facility. Data center operators have this obligation to fully understand how climate change affects their facilities and their customers. They may find that a mix of solutions will be adequate to address their needs today, while other more radical solutions are needed for tomorrow.  Climate change, or whatever you wish to call it, is here… now.

Related Resources from Uptime Institute:

  • Research Report: A Mission-Critical Industry Unprepared for Climate Change
  • Executive Insights: Climate Change and the Risk to Data Centers
  • Product Overview: Uptime Institute Data Center Assessments

Share this:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on LinkedIn (Opens in new window) LinkedIn
  • Share on Reddit (Opens in new window) Reddit
  • Share on WhatsApp (Opens in new window) WhatsApp
  • Email a link to a friend (Opens in new window) Email
Tags: Climate Change, Data Center Availability, Data Center Disaster Recovery
https://journal.uptimeinstitute.com/wp-content/uploads/2019/01/Flooding-Hurricane-ClimateChange-851x360.jpg 390 851 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2019-01-16 15:13:322019-01-16 15:13:32“Think Globally, Act Locally”: Re-Evaluating Data Center Resiliency in the Face of Climate Change
You might also like
Dual-Corded-Power Dual-Corded Power and Fault Tolerance: Past, Present, and Future
U.S. Bank Upgrades Its Data Center Electrical Distribution
Identifying Lurking Vulnerabilities in the World’s Best-Run Data Centers
Data center cost Data Center Cost Myths: SCALE
FORTRUST Gains Competitive Advantage from Management and Operations
Meeting the M&O Challenge of Managing a Diverse Data Center Footprint: John Sheputis and Don Jenkins, Infomart
Japan’s Biggest Provider of Critical IT Services Earns M&O Stamp of Approval
99 Red Flags: The Availability Nines 99 Red Flags

Content Categories

  • Journal Home
  • Executive
  • Operations
  • Design

Subscribe to Journal via Email

Enter your email address to subscribe to Uptime Institute Journal and receive notifications of new articles by email.

  • Recent

Tags

Accredited Tier Designer (9) AI (24) artificial intelligence (19) ATD (10) Carbon Emissions (7) Climate Change (13) Cloud (23) Cloud Computing (17) Cloud Costs (15) Cloud Infrastructure (29) Cloud Migration (8) Colocation (7) cooling (13) Data Center (261) Data Center Availability (40) Data Center Cooling (13) Data Center Design (45) Data Center Disaster Recovery (7) Data Center Energy Efficiency (34) Data Center Facilities Management (43) Data Center Operations (67) data center power (9) Data Center Staffing (19) DCIM (9) digital Infrastructure (126) energy (8) Energy Efficiency (38) Environmental Sustainability (18) IT (7) IT Efficiency (17) IT Outages (10) M&O (6) outages (12) Public Cloud (7) PUE (10) Regulations (25) Resiliency (9) security (7) Sustainability (34) Sustainability Reporting (7) Tier Certification (26) Tier Certification Constructed Facility (16) Uptime Institute FORCSS (6) Uptime Institute Network (13) Uptime Institute Symposium (6)
© 2014-2025 Uptime Institute, LLC All rights reserved.
  • Link to X
  • Link to LinkedIn
  • Link to Mail
Link to: NEXTDC: Obsessed with the details so our customers’ business is always available Link to: NEXTDC: Obsessed with the details so our customers’ business is always available NEXTDC: Obsessed with the details so our customers’ business is always... Link to: Data Center AI (Artificial Intelligence) Creates New Risks Link to: Data Center AI (Artificial Intelligence) Creates New Risks Data Center AI Creates New RisksGettyData Center AI (Artificial Intelligence) Creates New Risks