• Link to X
  • Link to LinkedIn
  • Link to Mail
  • ABOUT UI
    • Business Partners
    • Careers
    • Contact Us
    • News & Press
    • Our Team
    • Press Releases
    • Branding Guidelines
  • CONTACT
Uptime Institute Blog
  • Journal
    • Journal Home
    • Executive
    • Operations
    • Design
  • AI Services
    • AI Infrastructure Advisory
    • AI Custom Support
  • Tier Certification
    • Overview
    • Design
    • Construction
    • Operations
    • Tier Gap Analysis
    • Prefabricated/Modular
    • Tier Certifications List
  • Professional Services
    • Overview
    • Infrastructure Services
    • Management and Operations Services
    • Energy and Sustainability Services
    • Consulting Services
  • Education
    • Course Details
    • Course Calendar
    • Competency & Confidence Assessments
    • Private Education
    • Graduate Roster
  • Events
    • Industry Events
    • Leadership Events
    • Network Events
  • Network
    • Overview
    • Network Calendar
    • Network Roster
    • Request Corporate Access
    • Request Guest Access
    • Uptime Network Portal
  • Intelligence
  • Clients
    • Client Stories
  • Resources
    • Data Center Industry Surveys
    • Ebooks
    • Journal Blog
    • Product Datasheets
    • Research & Reports
    • Tier Specification Documents
    • Tools
    • Webinars
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu

Design


Capacity allocation and the next generation of AI-era KPIs

Capacity allocation and the next generation of AI-era KPIs

May 20, 2026/in Design, Executive, Operations/by Dr. Rand Talib, Research Analyst, Uptime Institute, rtalib@uptimeinstitute.com

AI workloads are reshaping data center infrastructure at an unprecedented scale. Rack densities exceeding 50 kW are becoming increasingly common. AI training clusters often operate near their peak power envelope for extended periods, placing sustained demand on facility infrastructure. At the same time, AI inference workloads exhibit different characteristics, often behaving more like traditional compute […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2026/05/Capacity_allocation_next_gen_AI-era_KPIs-featured.jpg 540 1030 Dr. Rand Talib, Research Analyst, Uptime Institute, rtalib@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Dr. Rand Talib, Research Analyst, Uptime Institute, rtalib@uptimeinstitute.com2026-05-20 15:00:002026-05-19 11:45:06Capacity allocation and the next generation of AI-era KPIs
Liquid cooling will not outgrow its high-density niche

Liquid cooling will not outgrow its high-density niche

April 15, 2026/in Design, Executive, Operations/by Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com

Deployment of direct liquid cooling (DLC, as cold plate or immersion systems) remains overwhelmingly concentrated in applications where air cooling is no longer a practical alternative. As a wave of AI infrastructure was being built, DLC manufacturers invested their engineering resources in maximizing cooling performance for high-performance IT — namely AI training hardware. By comparison, […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2026/04/Liquid-cooling-not-outgrow-high-density-niche-featured.jpg 540 1030 Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com2026-04-15 15:00:002026-04-14 15:06:46Liquid cooling will not outgrow its high-density niche
As emissions soar, operators look to carbon capture

As emissions soar, operators look to carbon capture

March 25, 2026/in Design, Executive, Operations/by Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com

During 2024 and 2025, a new trend emerged: many large data center builders and operators reported increases in their Scope 2, location- and market-based greenhouse gas (GHG) emissions inventories, reversing their efforts toward net-zero commitments. While this shift does not indicate a loss of commitment to those goals, it is an inevitable result of the […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2026/03/As-emissions-soar-operators-look-to-carbon-capture-featured.jpg 540 1030 Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com2026-03-25 15:00:002026-03-24 15:44:38As emissions soar, operators look to carbon capture

AI in data: sorting reality from hallucination

February 20, 2026/in Design, Executive, Operations/by Dr. Rand Talib, Research Analyst, Uptime Institute, rtalib@uptimeinstitute.com

Many people do not use the term artificial intelligence correctly: vendors, investors, and even some operators label everything from basic automation scripts to deep learning controllers as AI. This inflation of the term has commercial and strategic motives. AI branding helps attract funding, creates differentiation in the market, and positions traditional analytics as cutting-edge solutions. […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2026/02/AI-in-data-sorting-reality-from-hallucination-featured.jpg 540 1030 Dr. Rand Talib, Research Analyst, Uptime Institute, rtalib@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Dr. Rand Talib, Research Analyst, Uptime Institute, rtalib@uptimeinstitute.com2026-02-20 15:00:002026-02-19 12:13:09AI in data: sorting reality from hallucination
AI and cooling: toward more automation

AI and cooling: toward more automation

January 29, 2026/in Design, Executive, Operations/by Dr. Rand Talib, Research Analyst, Uptime Institute, rtalib@uptimeinstitute.com

AI is increasingly steering the data center industry toward new operational practices, where automation, analytics and adaptive control are paving the way for “dark” — or lights-out, unstaffed — facilities. Cooling systems, in particular, are leading this shift. Yet despite AI’s positive track record in facility operations, one persistent challenge remains: trust. In some ways, […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2026/01/AI-and-cooling-toward-more-automation-featured.jpg 540 1030 Dr. Rand Talib, Research Analyst, Uptime Institute, rtalib@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Dr. Rand Talib, Research Analyst, Uptime Institute, rtalib@uptimeinstitute.com2026-01-29 15:00:002026-01-28 09:58:29AI and cooling: toward more automation
AI’s growth calls for useful IT efficiency metrics

AI’s growth calls for useful IT efficiency metrics

January 15, 2026/in Design, Executive, Operations/by Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com

The digital infrastructure industry is under pressure to measure and improve the energy efficiency of the computing work that underpins digital services. Enterprises seek to maximize returns on cost outlay and operating expenses for IT hardware, and regulators and local communities need reassurance that the energy devoted to data centers is used efficiently. These objectives […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2026/01/AIs-growth-calls-for-useful-IT-efficiency-metrics-featured.jpg 540 1030 Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com2026-01-15 15:00:002026-01-14 11:41:16AI’s growth calls for useful IT efficiency metrics
AI power fluctuations strain both budgets and hardware

AI power fluctuations strain both budgets and hardware

December 17, 2025/in Design, Executive, Operations/by Douglas Donnellan, Senior Research Associate, Uptime Institute, ddonnellan@uptimeinstitute.com

AI training at scale introduces power consumption patterns that can strain both server hardware and supporting power systems, shortening equipment lifespans and increasing the total cost of ownership (TCO) for operators. These workloads can cause GPU power draw to spike briefly, even for only a few milliseconds, pushing them past their nominal thermal design power […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2025/12/AI-power-fluctuations-strain-budgets-hardware-featured.jpg 540 1030 Douglas Donnellan, Senior Research Associate, Uptime Institute, ddonnellan@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Douglas Donnellan, Senior Research Associate, Uptime Institute, ddonnellan@uptimeinstitute.com2025-12-17 15:00:002025-12-16 15:00:30AI power fluctuations strain both budgets and hardware
Electrical considerations with large AI compute

Electrical considerations with large AI compute

November 19, 2025/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

The training of large generative AI models is a special case of high-performance computing (HPC) workloads. This is not simply due to the reliance on GPUs — numerous engineering and scientific research computations already use GPUs as standard. Neither is it about the power density or the liquid cooling of AI hardware, as large HPC […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2025/11/Electrical-considerations-with-large-AI-compute-featured.jpg 540 1030 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2025-11-19 15:00:002025-11-18 10:08:46Electrical considerations with large AI compute
Is this the data center metric for the 2030s?

Is this the data center metric for the 2030s?

November 5, 2025/in Design, Executive, Operations/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

When the PUE metric was first proposed and adopted at a Green Grid meeting in California in 2008, few could have forecast how important this simple ratio — despite its limitations — would become. Few would have expected, too, that the industry would make so little progress on another metric proposed at those same early […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2025/11/Is-this-the-data-center-metric-for-the-2030s-featured.jpg 540 1030 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2025-11-05 12:00:002025-11-04 10:40:36Is this the data center metric for the 2030s?
Crypto mines are turning into AI factories

Crypto mines are turning into AI factories

October 22, 2025/in Design, Executive, Operations/by Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com

The pursuit of training ever-larger generative AI models has necessitated the creation of a new class of specialized data centers — facilities that have more in common with high-performance computing (HPC) environments than traditional enterprise IT. These data centers support very high rack densities (130 kW and above with current Nvidia rack-scale systems), direct-to-chip liquid […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2025/10/Crypto-mines-are-turning-into-AI-factories-featured.jpg 540 1030 Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com2025-10-22 15:00:002025-10-20 16:20:24Crypto mines are turning into AI factories
Cloud: when high availability hurts sustainability

Cloud: when high availability hurts sustainability

September 24, 2025/in Design, Executive, Operations/by Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com

In recent years, the environmental sustainability of IT has become a significant concern for investors and customers, as well as regulatory, legislative and environmental stakeholders. This concern is expected to intensify as the impact of climate change on health, safety and the global economy becomes more pronounced. It has given rise to an assortment of […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2025/09/Cloud-when-high-availability-hurts-sustainability-featured.jpg 540 1030 Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com2025-09-24 15:00:002025-09-23 13:02:36Cloud: when high availability hurts sustainability
Self-contained liquid cooling: the low-friction option

Self-contained liquid cooling: the low-friction option

September 10, 2025/in Design, Executive, Operations/by Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com

Each new generation of server silicon is pushing traditional data center air cooling closer to its operational limits. In 2025, the thermal design power (TDP) of top-bin CPUs reached 500 W, and server chip product roadmaps indicate further escalation in pursuit of higher performance. To handle these high-powered chips, more IT organizations are considering direct […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2025/09/Self-contained-liquid-cooling-featured.jpg 540 1030 Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com2025-09-10 15:00:002025-09-10 09:33:59Self-contained liquid cooling: the low-friction option
Are data centers to blame for power quality issues?

Are data centers to blame for power quality issues?

July 16, 2025/in Design, Executive, Operations/by Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com

Many grid operators are struggling to meet customer power demands — in both volume and quality. As demand rises, utilities must also monitor and account for customer usage patterns that can degrade power quality (and add costs) for others on the grid. A 2024 Bloomberg analysis revealed a concentration of residential power issues occurring near […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2025/07/Are_data_centers_to_blame_for_power_quality_issues-blog_hero_image_1030x540px-1.jpg 540 1030 Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com2025-07-16 15:00:002025-07-16 13:59:26Are data centers to blame for power quality issues?
Density choices for AI training are increasingly complex

Density choices for AI training are increasingly complex

June 25, 2025/in Design, Executive/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

When it comes to generative AI models, the belief that bigger is better is an enduring one — shaping a wide array of high-stakes decisions from corporate investments to energy and permitting policy to technology export controls. A defining technical feature in the pursuit of ever-bigger models is denser compute hardware. This makes sense: as […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2025/06/Density-choices-for-AI-training-are-increasingly-complex-featured.jpg 540 1030 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2025-06-25 15:00:002025-06-25 10:33:11Density choices for AI training are increasingly complex
Water is local: generalities do not apply

Water is local: generalities do not apply

May 28, 2025/in Design, Executive, Operations/by Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com

Water use has become a benchmark metric for data center operational efficiency and sustainability, as well as a frequent target of community criticism. Operators should track and optimize their water use to protect the environment and secure the facility cooling’s autonomy when its capacity relies on water. However, water use does not fit into a […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2025/05/Water-is-local-generalities-do-not-apply-featured.jpg 540 1030 Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com2025-05-28 15:00:002025-05-27 14:03:14Water is local: generalities do not apply
IT efficiency: an untapped power resource

IT efficiency: an untapped power resource

March 12, 2025/in Design, Executive, Operations/by Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com

Projections of data center capacity growth have exploded with the emergence of AI infrastructure and the continuing expansion and integration of standard IT functionality into the global economy. Electricity demand is growing in developed markets for the first time in more than a decade, led by proposed data center expansions and efforts to electrify the […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2025/03/IT-efficiency-untapped-power-resource-featured.jpg 540 1030 Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com2025-03-12 15:00:002025-03-11 14:01:18IT efficiency: an untapped power resource
How AWS’s own silicon and software deliver cloud scalability

How AWS’s own silicon and software deliver cloud scalability

February 12, 2025/in Design, Executive, Operations/by Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com

Amazon Web Services (AWS) was the world’s first hyperscale cloud provider, and it remains the largest today. It represents around one-third of the global market, offering more than 200 infrastructure, platform and software services across 34 regions. To efficiently deliver so many services at such a scale, AWS designs and builds much of its own […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2025/02/AWS-silicon-software-cloud-scalability-featured.jpg 540 1030 Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com2025-02-12 15:00:002025-02-12 10:02:45How AWS’s own silicon and software deliver cloud scalability
Water cold plates lead in the small, but growing, world of DLC

Water cold plates lead in the small, but growing, world of DLC

October 30, 2024/in Design, Executive, Operations/by Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com

Direct liquid cooling (DLC), including cold plate and immersion systems, is becoming more common in data centers — but so far this transition has been gradual and unevenly distributed with some data centers using it widely, others not at all. The use of DLC in 2024 still accounts for only a small minority of the […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2024/10/Water-cold-plates-lead-in-the-small-but-growing-world-of-DLC-featured.jpg 540 1030 Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com2024-10-30 15:00:002024-11-13 10:21:48Water cold plates lead in the small, but growing, world of DLC
OT protection: is air-gapping the answer?

OT protection: is air-gapping the answer?

October 21, 2024/in Design, Executive, Operations/by Michael O’Neil, Consulting Analyst - Cybersecurity, Uptime Institute, moneil@uptimeinstitute.com

Cyberattacks on operational technology (OT) were virtually unknown until five years ago, but their volume has been doubling since 2009. This threat is distinct from IT-focused vulnerabilities that cybersecurity measures regularly address. The risk associated with OT compromise is substantial: power or cooling failures can cripple an entire facility, potentially for weeks or months. Many […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2024/10/OT-Protection-Is-Air-Gapping-the-Answer-featured.jpg 540 1030 Michael O’Neil, Consulting Analyst - Cybersecurity, Uptime Institute, moneil@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Michael O’Neil, Consulting Analyst - Cybersecurity, Uptime Institute, moneil@uptimeinstitute.com2024-10-21 15:00:002024-11-13 10:23:12OT protection: is air-gapping the answer?
Managing server performance for power: a missed opportunity

Managing server performance for power: a missed opportunity

September 18, 2024/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

An earlier Uptime Intelligence report discussed the characteristics of processor power management (known as C-states) and explained how they can reduce server energy consumption to make substantial contributions to the overall energy performance and sustainability of data center infrastructure (see Understanding how server power management works). During periods of low activity, such features can potentially […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2024/09/Managing-server-performance-for-power-a-missed-opportunity-featured.jpg 540 1030 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2024-09-18 15:00:002024-09-17 15:35:54Managing server performance for power: a missed opportunity
Resiliency v low PUE: regulators a catalyst for innovation?

Resiliency v low PUE: regulators a catalyst for innovation?

September 4, 2024/in Design, Executive, Operations/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

Research has shown that while data center owners and operators are mostly in favor of sustainability regulation, they have a low opinion of the regulators’ expertise. Some operators have cited Germany’s Energy Efficiency Act as evidence: the law lays down a set of extremely challenging power usage effectiveness (PUE) requirements that will likely force some […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2024/09/Resiliency-v-low-PUE-regulators-a-catalyst-for-innovation-featured.jpg 540 1030 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2024-09-04 12:00:002024-09-06 14:47:55Resiliency v low PUE: regulators a catalyst for innovation?
Understanding how server power management works

Understanding how server power management works

July 10, 2024/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

Uptime Intelligence regularly addresses IT infrastructure efficiency, particularly servers, in our reports on data center energy performance and sustainability. Without active contribution from IT operations, facility operations alone will not be able to meet future energy and sustainability demands on data center infrastructure. Purchases of renewable energy and renewable energy certificates will become increasingly — […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2024/07/Understanding-how-server-power-management-works-featured.jpg 540 1030 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2024-07-10 15:00:002025-10-28 12:50:13Understanding how server power management works
What does embedded carbon of IT really represent?

What does embedded carbon of IT really represent?

May 8, 2024/in Design, Executive, Operations/by Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com

Due to regulatory mandates and expanded stakeholder expectations, a growing share of operators are quantifying and publicly reporting a complete carbon dioxide equivalent (CO2e) emissions inventory for their data center infrastructure. An organization’s direct on-site emissions (classified as Scope 1 according to the Greenhouse Gas Protocol) and emissions from purchased energy sources (classified as Scope […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2024/05/What-does-embedded-carbon-really-represent-featured.jpg 539 1030 Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com2024-05-08 15:00:002024-05-07 10:02:05What does embedded carbon of IT really represent?
DLC will not come to the rescue of data center sustainability

DLC will not come to the rescue of data center sustainability

April 25, 2024/in Design, Executive, Operations/by Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com

A growing number of data center operators and equipment vendors are anticipating the proliferation of direct liquid cooling systems (DLC) over the next few years. As far as projections go, Uptime Institute’s surveys agree: the industry consensus for the mainstream adoption of liquid-cooled IT converges on the latter half of the 2020s. DLC systems, such […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2024/04/DLC-will-not-come-to-the-rescue-of-data-center-sustainability-featured.jpg 539 1030 Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com2024-04-25 15:00:002024-04-24 13:58:20DLC will not come to the rescue of data center sustainability
Performance expectations of liquid cooling need a reality check

Performance expectations of liquid cooling need a reality check

March 20, 2024/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

The idea of using liquids to cool IT hardware, exemplified by technologies such as cold plates and immersion cooling, is frequently hailed as the ultimate solution to the data center’s energy efficiency and sustainability challenges. If a data center replaces air cooling with direct liquid cooling (DLC), chilled water systems can operate at higher supply […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2024/03/Performance-expectations-of-liquid-cooling-need-a-reality-check-featured.jpg 539 1030 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2024-03-20 15:00:002025-10-28 12:47:56Performance expectations of liquid cooling need a reality check
FinOps gives hope to those struggling with cloud costs

FinOps gives hope to those struggling with cloud costs

March 6, 2024/in Design, Executive, Operations/by John O’Brien, Senior Research Analyst, Uptime Institute, jobrien@uptimeinstitute.com

Cloud workloads are continuing to grow — sometimes adding to traditional on-premises workloads, sometimes replacing them. The Uptime Institute Global Data Center Survey 2023 shows that organizations expect the public cloud to account for 15% of their workloads by 2025. When private cloud hosting and software as a service (SaaS) are included, this share rises […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2024/03/FinOps-gives-hope-with-cloud-costs-featured.jpg 539 1030 John O’Brien, Senior Research Analyst, Uptime Institute, jobrien@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png John O’Brien, Senior Research Analyst, Uptime Institute, jobrien@uptimeinstitute.com2024-03-06 15:00:002025-10-28 12:43:41FinOps gives hope to those struggling with cloud costs
What role might generative AI play in the data center?

What role might generative AI play in the data center?

January 10, 2024/in Design, Executive, Operations/by John O’Brien, Senior Research Analyst, Uptime Institute, jobrien@uptimeinstitute.com

This is the first in a series of reports on artificial intelligence (AI) and its impact on the data center sector.

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2024/01/What-role-might-generative-AI-play-in-the-data-center-featured.jpg 539 1030 John O’Brien, Senior Research Analyst, Uptime Institute, jobrien@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png John O’Brien, Senior Research Analyst, Uptime Institute, jobrien@uptimeinstitute.com2024-01-10 15:00:002024-01-08 11:35:25What role might generative AI play in the data center?
Looking for the x-factor in data center efficiency

Looking for the x-factor in data center efficiency

December 13, 2023/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

The suitability of a data center environment is primarily judged by its effect on the long-term health of IT hardware. Facility operators define their temperature and humidity set points with a view to balancing hardware failure rates against the associated capital and operational expenditures, with the former historically prioritized. Over the past decade, this balance […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/12/Looking-for-the-x-factor-in-data-center-efficiency-v2-featured.jpg 539 1030 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2023-12-13 15:00:002024-01-24 09:18:10Looking for the x-factor in data center efficiency
Emerging regulatory requirements: tactics for riding the tsunami

Emerging regulatory requirements: tactics for riding the tsunami

November 16, 2023/in Design, Executive, Operations/by Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com

Over the past 12 months, Uptime Institute Intelligence has been closely following regulatory developments in the area of sustainability. These include mandates based on the Task force on Climate-related Financial Disclosure standard, such as the EU’s Corporate Sustainability Reporting Directive and the UK’s Climate-related Financial Disclosure Regulations, and the EU’s Energy Efficiency Directive. These legal […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/11/Emerging-regulatory-requirements-tactics-for-riding-the-tsunami-featured.jpg 539 1030 Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com2023-11-16 15:00:002023-11-15 13:55:30Emerging regulatory requirements: tactics for riding the tsunami
AI will have a limited role in data centers — for now

AI will have a limited role in data centers — for now

September 6, 2023/in Design, Executive, Operations/by Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com

The topic of artificial intelligence (AI) has captured the public’s imaginations, and now barely a week goes by without reports of another breakthrough. Among the many, sometimes dramatic predictions made by experts and non-experts alike is the potential elimination of some, or even many, jobs. These expectations are partly — but only partly — mirrored […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/09/AI-limited-role-for-now-featured.jpg 539 1030 Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com2023-09-06 15:00:002023-09-06 09:22:08AI will have a limited role in data centers — for now
The strong case for power management

The strong case for power management

August 23, 2023/in Design, Executive, Operations/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

ANALYST OPINION In a recent report on server energy efficiency, Uptime Intelligence’s Dr. Tomas Rahkonen analyzed data from 429 servers and identified five key insights (see Server energy efficiency: five key insights). All were valuable observations for better managing (and reducing) IT power consumption, but one area of his analysis stood out: the efficiency benefits […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/08/The-strong-case-for-power-management-featured.jpg 539 1030 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2023-08-23 15:00:002023-08-22 09:25:21The strong case for power management
Cloud resiliency: plan to lose control of your planes

Cloud resiliency: plan to lose control of your planes

June 14, 2023/in Design, Executive, Operations/by Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com

Cloud providers divide the technologies that underpin their services into two ”planes”, each with a different architecture and availability goal. The control plane manages resources in the cloud; the data plane runs the cloud buyer’s application. In this Update, Uptime Institute Intelligence presents research that shows control planes have poorer availability than data planes. This […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/06/Cloud-resiliency-plan-to-lose-control-of-your-planes-featured.jpg 539 1030 Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com2023-06-14 15:00:002023-06-13 17:26:33Cloud resiliency: plan to lose control of your planes
Server efficiency increases again — but so do the caveats

Server efficiency increases again — but so do the caveats

June 7, 2023/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

Early in 2022, Uptime Intelligence observed that the return of Moore’s law in the data center (or, more accurately, the performance and energy efficiency gains associated with it) would come with major caveats (see Moore’s law resumes — but not for all). Next-generation server technologies’ potential to improve energy efficiency, Uptime Intelligence surmised at the […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/06/Server-efficiency-and-caveats-increases-again-featured.jpg 539 1030 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2023-06-07 15:00:002023-06-06 16:14:48Server efficiency increases again — but so do the caveats
Cooling to play a more active role in IT performance and efficiency

Cooling to play a more active role in IT performance and efficiency

May 24, 2023/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

Data center operators and IT tenants have traditionally adopted a binary view of cooling performance: it either meets service level commitments, or it does not. The relationship is also coldly transactional: as long as sufficient volumes of air of the right temperature and quality (in accordance with service-level agreements that typically follow ASHRAE’s guidance) reach […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/05/Cooling-to-play-a-more-active-role-in-IT-performance-and-efficiency-featured.jpg 539 1030 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2023-05-24 15:00:002023-05-22 14:23:53Cooling to play a more active role in IT performance and efficiency
Energy-efficiency focus to shift to IT — at last

Energy-efficiency focus to shift to IT — at last

May 3, 2023/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

Data centers have become victims of their own success. Ever-larger data centers have mushroomed across the globe in line with an apparently insatiable demand for computing and storage capacity. The associated energy use is not only expensive (and generating massive carbon emissions) but is also putting pressure on the grid. Most data center developments tend […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/05/Energy-efficiency-focus-to-shift-to-IT-at-last-featured.jpg 539 1030 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2023-05-03 15:00:002023-05-02 11:33:58Energy-efficiency focus to shift to IT — at last
Forecasting the solar storm threat

Forecasting the solar storm threat

April 19, 2023/in Design, Executive, Operations/by Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com

A proposed permanent network of electromagnetic monitoring stations across the continental US, operating in tandem with a machine learning (ML) algorithm, could facilitate accurate predictions of geomagnetic disturbances (GMDs). If realized, this predictive system could help grid operators avert disruption and reduce the likelihood of damage to their — and their customers’ — infrastructure, including […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/04/Forecasting-the-Solar-Storm-Threat-featured.jpg 539 1030 Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com2023-04-19 15:00:002023-04-18 10:29:17Forecasting the solar storm threat
Data center costs set to rise and rise

Data center costs set to rise and rise

March 29, 2023/in Design, Executive, Operations/by Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com

Up until two years ago, the cost of building and operating data centers had been falling reasonably steeply. Improving technology, greater production volumes as the industry expanded and consolidated, large-scale builds, prefabricated and modular construction techniques, stable energy prices and the low costs of capital have all played a part. While labor costs have risen […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/03/Data-center-costs-set-to-rise-and-rise-featured.jpg 539 1030 Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com2023-03-29 15:00:002023-03-27 12:20:19Data center costs set to rise and rise
Too hot to handle? Operators to struggle with new chips

Too hot to handle? Operators to struggle with new chips

March 15, 2023/in Design, Executive, Operations/by Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com

Standard IT hardware was a boon for data centers: for almost two decades, mainstream servers have had relatively constant power and cooling requirements. This technical stability moored the planning and design of facilities (for both new builds and retrofits) and has helped attract investment in data center capacity and technical innovation. Furthermore, many organizations are […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/03/Too-hot-to-handle-Operators-to-struggle-with-new-chips-featured.jpg 539 1030 Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com2023-03-15 15:00:002023-03-14 09:42:37Too hot to handle? Operators to struggle with new chips
Unravelling net zero

Unravelling net zero

February 22, 2023/in Design, Executive, Operations/by Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com

Many digital infrastructure operators have set themselves carbon-neutral or net-zero emissions goals: some large hyperscale operators claim net-zero emissions for their current operating year. Signatories to the Climate Neutral Data Center Pact, a European organization for owners and operators, aim to be using 100% clean energy by 2030. All these proclamations appear laudable and seem […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/02/Unraveling-net-zero-featured.jpg 539 1030 Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com2023-02-22 13:00:002023-02-22 09:48:39Unravelling net zero
Major data center fire highlights criticality of IT services

Major data center fire highlights criticality of IT services

January 11, 2023/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

Uptime Institute’s outages database suggests data center fires are infrequent, and rarely have a significant impact on operations. Uptime has identified 14 publicly reported, high-profile data center outages caused by fire or fire suppression systems since 2020. The frequency of fires is not increasing relative to the IT load or number of data centers but, […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2023/01/Major-data-center-fire-highlights-criticality-of-IT-services-featured.jpg 539 1030 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2023-01-11 13:00:002023-01-10 15:40:40Major data center fire highlights criticality of IT services
Rising energy prices

Will high energy prices push operators to direct liquid cooling?

November 16, 2022/in Design, Executive, Operations/by Lenny Simon, Senior Research Associate, Uptime Institute

The data center industry and other large power-consuming industries continue to feel pressure from skyrocketing electricity prices. In Germany and France, wholesale energy prices this August increased six-fold compared to prices from 2021. The US has fared better, but wholesale electricity prices have doubled this summer compared with last year’s prices. While leased data center […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/11/Rising-Energy-Prices-featured.jpg 628 1200 Lenny Simon, Senior Research Associate, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Lenny Simon, Senior Research Associate, Uptime Institute2022-11-16 08:00:002022-11-08 15:09:24Will high energy prices push operators to direct liquid cooling?
Data centers weather solar storms

Data centers weather solar storms

October 19, 2022/in Design, Executive, Operations/by Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com

The US Space Weather Prediction Center (SWPC) issued multiple geomagnetic storm watches throughout August and September 2022. Geomagnetic storms occur when solar storms interact with the Earth’s atmosphere and magnetic field, risking disruption to satellites, radio communications and the power grid. The strongest predicted storm earned the agency’s rating of G3 (“strong”) on a five-level […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/10/Solar-Storms-featured.jpg 628 1200 Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com2022-10-19 08:00:002022-10-05 16:14:07Data centers weather solar storms
Quantum Computing

Quantum computing is not a panacea yet

October 5, 2022/in Design, Executive, Operations/by Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com

Quantum computing promises a revolution in scientific discovery. Quantum computing’s main advantage over digital computing is in quickly solving highly complex problems that require significant time or resources to process. Currently, solutions to many complex problems can be estimated using supercomputers or pools of servers over days or weeks. Other problems are so complex that […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/09/Quantum-Computing-featuring.jpg 628 1200 Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, orogers@uptimeinstitute.com2022-10-05 08:00:002022-09-14 14:25:39Quantum computing is not a panacea yet
Vegetable oil promises a sustainable alternative to diesel

Vegetable oil promises a sustainable alternative to diesel

September 14, 2022/in Design, Operations/by Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com

The thousands of gallons of diesel that data centers store on-site to fuel backup generators in the event of a grid outage are hard to ignore — and do little to assist operators’ drive toward tougher sustainability goals. In the past two years, an alternative to diesel made from renewable materials has found support among […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/09/HVO-hydrotreated-vegatable-oil-featured.jpg 628 1200 Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Max Smolaks, Research Analyst, msmolaks@uptimeinstitute.com2022-09-14 08:00:002022-09-12 15:46:56Vegetable oil promises a sustainable alternative to diesel
Sustainability laws set to drive real change

Sustainability laws set to drive real change

August 31, 2022/in Design, Executive, Operations/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

Nearly 15 years ago – in 2008 – Uptime Institute presented a paper titled “The gathering storm.” The paper was about the inevitability of a struggle against climate change and how this might play out for the power-hungry data center and IT sector. The issues were explored in more detail in the 2020 Uptime Institute […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/08/Sustainability-Laws-featured.jpg 628 1200 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2022-08-31 03:00:002022-08-22 10:20:36Sustainability laws set to drive real change
Equipment shortages may ease soon — but not for good reasons

Equipment shortages may ease soon — but not for good reasons

August 24, 2022/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

When Uptime Institute Intelligence surveyed data center infrastructure operators about supply chain issues in August 2021, more than two-thirds of respondents had experienced some shortages in the previous 18 months. Larger operations bore the brunt of disruptions, largely due to shortages or delays in sourcing major electrical equipment (such as switchgear, engine generators and uninterruptible […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/08/Weak-Demand-featured.jpg 628 1200 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2022-08-24 08:00:002022-08-15 14:09:19Equipment shortages may ease soon — but not for good reasons
Extreme heat stress-tests European data centers – again

Extreme heat stress-tests European data centers – again

July 27, 2022/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

An extreme heat wave swept across much of Western Europe on July 18 and 19, hitting some of the largest metropolitan areas such as Frankfurt, London, Amsterdam and Paris — which are also global data center hubs with hundreds of megawatts of capacity each. In the London area, temperatures at Heathrow Airport surpassed 40°C / […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/07/Extreme-heat-featured.jpg 628 1200 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2022-07-27 20:37:472022-07-28 10:23:38Extreme heat stress-tests European data centers – again
Crypto data centers: The good, the bad and the electric

Crypto data centers: The good, the bad and the electric

July 27, 2022/in Design, Executive, Operations/by Lenny Simon, Senior Research Associate, Uptime Institute

A single tweet in May 2021 brought unprecedented public attention to a relatively unknown issue. Tesla CEO Elon Musk tweeted that because of the large energy consumption associated with the use of Bitcoin, Tesla would no longer accept it as currency. Instead, Tesla would favor other cryptocurrencies that use less than 1% of Bitcoin’s energy […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/07/Crypto-data-centers-featured.jpg 628 1200 Lenny Simon, Senior Research Associate, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Lenny Simon, Senior Research Associate, Uptime Institute2022-07-27 08:00:002022-07-18 14:09:06Crypto data centers: The good, the bad and the electric
Direct liquid cooling (DLC): pressure is rising but constraints remain

Direct liquid cooling: pressure is rising but constraints remain

July 6, 2022/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

Direct liquid cooling (DLC) is a collection of techniques that removes heat by circulating a coolant to IT electronics. Even though the process is far more efficient than using air, the move to liquid cooling has been largely confined to select applications in high-performance computing to cool extreme high-density IT systems. There are a few […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/06/Direct-liquid-cooling-pressure-is-rising-but-constraints-remain-featured.jpg 628 1200 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2022-07-06 08:00:002025-10-28 12:25:48Direct liquid cooling: pressure is rising but constraints remain
The ultimate liquid cooling: heat rejection into water

The ultimate liquid cooling: heat rejection into water

June 29, 2022/in Design, Executive, Operations/by Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com

Uptime Institute’s data on power usage effectiveness (PUE) is a testament to the progress the data center industry has made in energy efficiency over the past 10 years. However, global average PUEs have been largely stalling at close to 1.6 since 2018, with only marginal gains. This makes sense: for the average figure to show […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/06/Ultimate-liquid-cooling-featured.jpg 628 1200 Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com2022-06-29 07:00:002022-06-17 15:22:44The ultimate liquid cooling: heat rejection into water
Direct liquid cooling bubbles to the surface

Direct liquid cooling bubbles to the surface

March 31, 2022/in Design, Executive, Operations/by Lenny Simon, Senior Research Associate, Uptime Institute

Conditions will soon be ripe for widespread use of direct liquid cooling (DLC) — a collection of techniques that uses fluid to remove heat from IT electronics instead of air — and it may even become essential. Currently, air cooling is still dominant with DLC remaining a niche option — around 85% of enterprise IT […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/03/DLC-direct-liquid-cooling-featured.jpg 628 1200 Lenny Simon, Senior Research Associate, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Lenny Simon, Senior Research Associate, Uptime Institute2022-03-31 06:00:002022-03-29 16:39:28Direct liquid cooling bubbles to the surface
Bring on regulations for data center sustainability, say Europe and APAC

Bring on regulations for data center sustainability, say Europe and APAC

January 12, 2022/in Design, Executive/by Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com

As the data center sector increases its focus on becoming more environmentally sustainable, regulators still have a part to play — the question is to what extent?

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2022/01/Sustainability-Regulations-featured.jpg 628 1200 Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com2022-01-12 07:00:002022-01-12 01:14:52Bring on regulations for data center sustainability, say Europe and APAC
Mixed resiliency at the edge

Mixed resiliency at the edge

November 17, 2021/in Design, Operations/by Dr. Tomas Rahkonen, Research Director of Distributed Data Centers, Uptime Institute

Many analysts have forecast an explosion in demand for edge data centers. After a long, slow start, demand is beginning to build, with small, prefabricated and mostly remotely operated data centers ready to be deployed to support a varying array of applications.

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2021/11/Mixed-Resiliency-Edge-featured.jpg 628 1200 Dr. Tomas Rahkonen, Research Director of Distributed Data Centers, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Dr. Tomas Rahkonen, Research Director of Distributed Data Centers, Uptime Institute2021-11-17 08:00:002021-11-16 09:07:48Mixed resiliency at the edge
Does the spread of direct liquid cooling make PUE less relevant?

Does the spread of direct liquid cooling make PUE less relevant?

November 5, 2021/in Design, Executive, Operations/by Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com

The power usage effectiveness (PUE) metric is predominant thanks to its universal applicability and its simplicity: energy used by the entire data center, divided by energy used by the IT equipment.

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2021/11/DLC-featured.jpg 628 1200 Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, jdavis@uptimeinstitute.com2021-11-05 08:30:002021-11-04 21:01:17Does the spread of direct liquid cooling make PUE less relevant?
ASHRAE Guidelines

New ASHRAE guidelines challenge efficiency drive

October 21, 2021/in Design, Executive, Operations/by Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com

Earlier in 2021, ASHRAE’s Technical Committee 9.9 published an update — the fifth edition — of its Thermal Guidelines for Data Processing Environments.

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2021/10/ASHRAE-Guidelines.jpg 600 1200 Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Daniel Bizo, Research Director, Uptime Institute Intelligence, dbizo@uptimeinstitute.com2021-10-21 10:15:512025-10-28 12:31:45New ASHRAE guidelines challenge efficiency drive
Eyeing an uptick in edge data center demand

Eyeing an uptick in edge data center demand

June 28, 2021/in Design, Executive/by Dr. Tomas Rahkonen, Research Director of Distributed Data Centers, Uptime Institute

Data center end-user organizations and suppliers alike expect an uptick in edge data center demand in the near term.

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2021/06/Edge-Data-Denter-Demand.jpg 428 1030 Dr. Tomas Rahkonen, Research Director of Distributed Data Centers, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Dr. Tomas Rahkonen, Research Director of Distributed Data Centers, Uptime Institute2021-06-28 05:00:002021-06-25 09:35:48Eyeing an uptick in edge data center demand
UI @ 2021

Green tariff renewable energy purchases

May 10, 2021/in Design, Executive/by Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com

Until recently, power purchase agreements (PPAs) and unbundled renewable energy certificates (RECs) were the primary means for data center operators or managers to procure renewable electricity and RECs for their operations. Many companies are not comfortable with the eight-to-20-year length and financial risks of a PPA. Unbundled RECs are an ongoing expense and do not […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2021/05/Green-energy3.jpg 612 1638 Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jay Dietrich, Research Director of Sustainability, Uptime Institute, jdietrich@uptimeinstitute.com2021-05-10 06:04:002025-10-30 13:31:14Green tariff renewable energy purchases
Datacenter fire frequency trends

Datacenter Fire Frequency

April 5, 2021/in Design, Executive, Operations/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

The catastrophic fire that occurred at OVHcloud’s SBG2 data center in Strasbourg, France (see last week’s blog about it) has led many operators to question their vulnerability to fires. Fires at data centers are a constant concern, but are rare. In almost all cases of data center fire, the source is quickly located, the equipment isolated, […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2021/04/fire3.jpg 692 1932 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2021-04-05 08:26:002025-10-30 13:30:46Datacenter Fire Frequency

Learning from the OVHcloud data center fire

March 29, 2021/in Design, Executive/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

The fire that destroyed a data center (and damaged others) at the OVHcloud facility in Strasbourg, France, on March 10-11, 2021, has raised a multitude of questions from concerned data center operators and customers around the world. Chief among these is, “What was the main cause, and could it have been prevented?” Fires at data […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2021/03/firefist2a.jpg 650 1819 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2021-03-29 06:01:002021-03-23 15:21:42Learning from the OVHcloud data center fire
UI 2021

Network problems causing ever more outages

February 22, 2021/in Design, Executive/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

Power failures have always been one of the top causes of serious IT service outages. The loss of power to a data center can be devastating, and its consequences have fully justified the huge expense and effort that go into preventing such events. But in recent years, other causes are catching up, with networking issues […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2021/02/dd2.jpg 899 2034 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2021-02-22 05:44:002025-10-30 12:55:00Network problems causing ever more outages
Critical Infrastructrure Innovation in 2021

A Surge of Innovation

January 18, 2021/in Design, Executive/by Rhonda Ascierto, Vice President, Research, Uptime Institute

Data center operators (and enterprise IT) are generally cautious adopters of new technologies. Only a few (beyond hyperscale operators) try to gain a competitive advantage through their early use of technology. Rather, they have a strong preference toward technologies that are proven, reliable and well-supported. This reduces risks and costs, even if it means opportunities […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2021/01/blog-1-18.jpg 627 1458 Rhonda Ascierto, Vice President, Research, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Rhonda Ascierto, Vice President, Research, Uptime Institute2021-01-18 05:00:002025-10-30 14:32:24A Surge of Innovation
UI @2021

Sustainability: More challenging, more transparent

January 11, 2021/in Design, Executive/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

Through 2021 and beyond, the world will begin to recover from its acute crisis — COVID-19 — and will turn its attention to other matters. Few if any of these issues will be as important as climate change, a chronic condition that will become more pressing and acute as each year passes. In the critical […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2021/01/sustainability2.jpg 242 700 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2021-01-11 05:42:002025-10-30 14:29:47Sustainability: More challenging, more transparent

Edge Computing – The Next Frontier

January 4, 2021/in Design, Executive/by Rhonda Ascierto, Vice President, Research, Uptime Institute

One of the most widely anticipated trends in IT and infrastructure is significant new demand for edge computing, fueled by technologies such as 5G, IoT and AI. To date, net new demand for edge computing — processing, storing and integrating data close to where it is generated — has built slowly. As a result, some […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/12/Edge5sm.jpg 235 645 Rhonda Ascierto, Vice President, Research, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Rhonda Ascierto, Vice President, Research, Uptime Institute2021-01-04 05:34:002025-10-30 14:28:34Edge Computing – The Next Frontier
UI 2020

Five Trends for 2021: accountability, automation, edge, sustainability, innovation

December 14, 2020/in Design, Executive, Operations/by Rhonda Ascierto, Vice President, Research, Uptime Institute

What we can expect for mission-critical digital infrastructure in 2021? Each autumn Uptime Institute, like many other organizations, puts together a list of some of the big trends and themes for the year ahead. This time, we have focused on five big trends that might not have been so obvious 12 months ago. Heading into […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/12/trends2021.jpg 684 2180 Rhonda Ascierto, Vice President, Research, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Rhonda Ascierto, Vice President, Research, Uptime Institute2020-12-14 06:00:072020-11-30 14:40:47Five Trends for 2021: accountability, automation, edge, sustainability, innovation

Rack Density is Rising

December 7, 2020/in Design, Executive/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

Density is rising The power density per rack (kilowatts [kW] per cabinet) is a critical number in data center design, capacity planning, and cooling and power provisioning. There have been industry warnings about a meteoric rise in IT equipment rack power density for the past decade (at least). One reason for this prediction is the […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/11/racks1.jpg 649 1923 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2020-12-07 06:00:562020-11-30 14:14:55Rack Density is Rising
UI 2020

COVID-19, air filtration and energy use

November 16, 2020/in Design, Executive/by Todd Traver

The COVID-19 pandemic has caused concerns about data center HVAC (heating, ventilation and air conditioning) filtration. So many data center operators are adjusting filtration protocols, including upgrading to finer MERV (minimum efficiency reporting value) 13 filters, to better filter out aerosols and COVID-19 virus carriers.1 But there is no free lunch. Depending on the design […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/10/ch1aa.jpg 500 1350 Todd Traver https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Todd Traver2020-11-16 05:00:502025-10-30 15:01:09COVID-19, air filtration and energy use
UI 2020

Why ASHRAE is concerned about edge data centers

November 9, 2020/in Design, Executive/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

There are few organizations that have had as big an impact on data center design as ASHRAE — and specifically, their Technical Committee (TC) 9.9. ASHRAE’s 2004 publication Thermal guidelines for Data Processing Environments (now in its fourth edition) described the optimal environmental operating conditions for the electronics in a data center, and in doing so, effectively […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/11/Edge1.jpg 920 2185 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2020-11-09 04:54:042020-10-29 08:36:15Why ASHRAE is concerned about edge data centers
UI 2020

Why data center operators are investing in more redundancy

October 26, 2020/in Design, Executive, Operations/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

When Uptime Institute recently asked over 300 data center managers how the pandemic would change their operations, one answer stood out: Two-thirds expect to increase the resiliency of their core data center(s) in the years ahead. Many said they expected their costs to increase as a result. The reasoning is clear: the pandemic — or […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/10/type1a.jpg 355 1475 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2020-10-26 06:00:342025-10-30 14:25:59Why data center operators are investing in more redundancy
2020

Increasing data center temperatures to reduce energy costs

October 12, 2020/in Design, Executive/by Mark Harris

Periodically we get questions about data center temperatures and energy savings. The questions usually ask about possible energy savings in commercial data centers by raising the temperature of the data hall. Some form of this question surfaces regularly over time because it just seems to be a common sense opportunity. But there is alot to […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/10/thermo3.jpg 735 2420 Mark Harris https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Mark Harris2020-10-12 06:00:522025-03-03 09:55:27Increasing data center temperatures to reduce energy costs
2020

Data Centers and Thunder, Lightning, Wind and Rain

September 28, 2020/in Design, Executive, Operations/by Chris Brown, Chief Technical Officer, Uptime Institute

Data centers are built and sited to withstand all that Mother Nature can throw at them — or at least, is likely to throw at them — during their lifecycle. This has long been a given, practiced and understood by designers, planners and regulators. But climate change is changing everything. Recent weather events have led […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/09/pexels-photo-1446076-blogsm.jpg 1165 3144 Chris Brown, Chief Technical Officer, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Chris Brown, Chief Technical Officer, Uptime Institute2020-09-28 06:00:522020-09-11 14:50:41Data Centers and Thunder, Lightning, Wind and Rain
UI @ 2020

Data Centers and Wildfires

September 16, 2020/in Design, Executive, Operations/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

As will be discussed in our upcoming note about managing data center with the severe weather caused by climate change, we continue to highlight the need for data center managers to not only review existing emergency plans but also anticipate previously unforeseen challenges. The need to understand the new ‘Normal’ Which brings us to wildfires… […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/10/pexels-sippakorn-yamkasikorn-3552472-blogsm.jpg 1394 3764 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2020-09-16 06:00:542020-09-14 09:43:03Data Centers and Wildfires
2020

Lithium-ion batteries in the Data Center: An ethical dimension?

September 6, 2020/in Design, Executive/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

One of the emerging trends in data centers is the use of lithium ion (Li-ion) batteries, both for distributed and centralized uninterruptible power supplies. Research by Uptime Institute and others predicts high levels of adoption in the years ahead. The primary reasons for this are technical, relating to energy density, rechargeability and management. But Li-ion […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/08/Lithium-Element-Blog.jpg 830 2255 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2020-09-06 06:00:082020-08-27 10:49:33Lithium-ion batteries in the Data Center: An ethical dimension?
2020

Which regions have the most energy efficient data centers?

August 24, 2020/in Design, Operations/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

When the PUE (Power Usage Effectiveness) metric for data centers was first agreed upon by the members of The Green Grid back in 2007, almost everyone in that crowded room in California agreed: This is not intended to be used as comparative metric across sites (as every situation is different) but it would be an […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/08/energy-Efficiency2.jpg 870 2500 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2020-08-24 06:00:242025-10-30 14:13:25Which regions have the most energy efficient data centers?
2020

Certifying the Tier performance data center… Remotely? Yes!

August 10, 2020/in Design/by Chris Brown, Chief Technical Officer, Uptime Institute

Mitigating Risk Now with Remote Delivery of Tier Certifications COVID-19 has changed the way we go about our lives and how we approach our work. We found ourselves—almost overnight—not traveling, not going into an office, figuring out how to stay home most of the time while continuing to work, and wondering why a respiratory infection […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/08/Remote-TCCF.jpg 925 2430 Chris Brown, Chief Technical Officer, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Chris Brown, Chief Technical Officer, Uptime Institute2020-08-10 06:00:042020-07-24 10:45:46Certifying the Tier performance data center… Remotely? Yes!
2020

Best-in-class data center provisioning: Simplify, Standardize, Repeat

July 13, 2020/in Design, Executive/by Rhonda Ascierto, Vice President, Research, Uptime Institute

Demand for IT capacity continues to grow rapidly across the globe, which has driven the need for more industrialized approaches to data center provisioning including construction and component assembly. Large operators and their partners have scrambled to apply new processes and disciplines, expand and re-organize supply chains, deploy prefabricated components, and, where possible, reduce cost […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/07/Blog-Provisioning.jpg 500 1350 Rhonda Ascierto, Vice President, Research, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Rhonda Ascierto, Vice President, Research, Uptime Institute2020-07-13 06:00:382020-07-06 13:36:33Best-in-class data center provisioning: Simplify, Standardize, Repeat
Micro Datacenter Growth in Slow Motion2020

Micro data centers: An explosion in demand, in slow motion

February 3, 2020/in Design, Executive/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

A wave of new technologies, from 5G to the internet of things (IoT) to artificial intelligence (AI), means much more computing and much more data will be needed near the point of use. That means many more small data centers will be required. But there will be no sudden mass deployment, no single standout use […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/01/GettyImages-157394357-blog.jpg 1024 2720 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2020-02-03 05:34:532025-10-30 15:20:40Micro data centers: An explosion in demand, in slow motion
Data Center Energy is Trending Upwards2019

Data center energy use goes up and up and up

January 6, 2020/in Design, Executive, Operations/by Rabih Bashroush

Energy use by data centers and IT will continue to rise, putting pressure on energy infrastructure and raising questions about carbon emissions. The drivers for more energy use are simply too great to be offset by efficiency gains. Drivers Demand for digital services has seen sustained, exceptional growth over the past few years — and […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2020/01/GettyImages-1096717338-blog.jpg 1762 4775 Rabih Bashroush https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Rabih Bashroush2020-01-06 06:00:422025-10-30 15:42:30Data center energy use goes up and up and up
Data Centers without Generators?2019

Data centers without diesel generators: The groundwork is being laid…

December 2, 2019/in Design, Executive/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

In 2012, Microsoft announced that it planned to eliminate engine generators at its big data center campus in Quincey, Oregon. Six years later the same group, with much the same aspirations, filed for permission to install 72 diesel generators, which have an expected life of at least a decade. This example illustrates clearly just how […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/11/datacenter-2-7.jpg 1513 4085 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2019-12-02 06:30:252025-11-12 11:19:07Data centers without diesel generators: The groundwork is being laid…
Lithium-Ion Batteries in the Data Center2019

Lithium Ion Batteries for the data center. Are they ready for production yet?

November 11, 2019/in Design/by Chris Brown, Chief Technical Officer, Uptime Institute

We are often asked for our thoughts about the use of lithium-ion (Li-ion) batteries in data center uninterruptible power supply (UPS) systems. This is a relatively new, evolving technology, and there are still a lot of unknowns. In our business, the unknown makes us nervous and uneasy — as it should, because we are tasked […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/11/Batteries-2-7.jpg 1923 5248 Chris Brown, Chief Technical Officer, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Chris Brown, Chief Technical Officer, Uptime Institute2019-11-11 06:00:122019-11-07 17:14:31Lithium Ion Batteries for the data center. Are they ready for production yet?
Free Air Cooling

Data Center Free Air Cooling Trends

September 9, 2019/in Design, Executive/by Rabih Bashroush

With the recent expansion of the American Society of Heating, Refrigerating and Air-Conditioning Engineers’ (ASHRAE’s) acceptable data center operating temperature and humidity ranges — taken as an industry-standard best practice by many operators — the case for free air cooling has become much stronger. Free air cooling is an economical method of using low external […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/09/BLOG-Energy-Arrows.jpg 801 2202 Rabih Bashroush https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Rabih Bashroush2019-09-09 06:30:542025-11-12 11:50:41Data Center Free Air Cooling Trends
Open19-Rack Platform

Open19 expects 2019 to be the year of “Accelerated Adoption”

August 5, 2019/in Design, Executive/by Kevin Heslin

We have heard for a dozen years about the Open Computing Project (OCP) and their non-traditional approach to computing hardware, from the racks to the servers, storage and networking. And over the last few years to the Open19 Foundation started to promote their alternative platform which resembles the more traditional 19-inch rack approach we have […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/06/Open19-Rack-Photo-wide.jpg 688 1883 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2019-08-05 09:00:032025-11-12 12:09:35Open19 expects 2019 to be the year of “Accelerated Adoption”
Climate Change changes all the norms

PG&E Turns Power Off (a.k.a. Climate Change and the Data Center)

July 29, 2019/in Design, Executive, Operations/by Kevin Heslin

In our October 2018 report, A mission-critical industry unprepared for climate change, Uptime Institute Intelligence urged data center operators and owners to plan for the effects of climate change. We specifically encouraged data center owners and operators to meet with government officials and utility executives to learn about local and regional disaster preparation and response plans. […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/05/carr-fire-gty-er-180731_hpMain-999x375.png 373 989 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2019-07-29 08:00:292019-07-07 06:18:23PG&E Turns Power Off (a.k.a. Climate Change and the Data Center)
Proposed Data Center building standard and batteriesGetty

Proposed NFPA 855 battery standard worries Data Center industry

June 27, 2019/in Design, News/by Kevin Heslin

A furious — but late — response to the National Fire Protection Association’s (NFPA’s) proposed standard 855, Standard for the Installation of Stationary Energy Storage, should put the whole data center industry on notice that it needs to increase its participation in standards development worldwide. This is not the first time professional bodies outside of […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/06/DC-FIREv2.jpg 1084 2994 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2019-06-27 10:00:142019-06-27 09:42:26Proposed NFPA 855 battery standard worries Data Center industry
The Business Case for Smart Power is ElusiveUptime Institute, 2019

The Business Case for Smart Energy is Still in the Making

June 18, 2019/in Design/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

Smart Energy is getting a lot of airplay in the data center world at present. New or planned products that fall under this broad banner include Energy-as-a-Service uninterruptible power supplies, software-defined power systems, and adaptable redundant systems that enable operators to raise or reduce their level of redundancy according to business needs. It might be […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/04/SMART-POWER.jpg 554 1177 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2019-06-18 09:00:262025-11-12 12:17:14The Business Case for Smart Energy is Still in the Making
The Renewed Push for Renewable EnergyGetty

Renewed Pressure for Renewables to Power the Data Center

June 10, 2019/in Design, Executive/by Kevin Heslin

In a recent presentation at the Energy Smart data center conference in Stockholm, Gary Cook, the Greenpeace activist who has tracked data center carbon emissions for a decade, showed a slide of logos, indicating companies that have made a commitment to use 100 percent renewable energy for their IT. Cook showed the commitment started with […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/04/RENEWABLE.jpg 568 1371 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2019-06-10 09:00:072025-11-12 12:22:57Renewed Pressure for Renewables to Power the Data Center
Server Virtualization Reduces Data Center Capacity RequirementsGetty

For most, virtualization reduces data center capacity demand more than anything else

May 30, 2019/in Design/by Rhonda Ascierto, Vice President, Research, Uptime Institute

The public cloud is dampening demand for data center capacity and leading to closures, consolidation and a big rethink on data center ownership. Right? Not quite, according to the latest Uptime Intelligence research. In enterprise and colocation data centers, we found that virtualization helps free up data center capacity more than any other technology or […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/04/VIRTUALIZATION.jpg 543 1260 Rhonda Ascierto, Vice President, Research, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Rhonda Ascierto, Vice President, Research, Uptime Institute2019-05-30 09:00:102025-11-12 12:27:21For most, virtualization reduces data center capacity demand more than anything else
Data Center Skills ShortageGetty Images

The Data Center Staffing and Skills Shortage is here NOW!

May 22, 2019/in Design, Executive, Operations/by Sandra Vail

Sometimes it can be hard to get people to talk about their issues — other times, it can be hard to keep them quiet. A recent Uptime Institute Network member’s meeting began as an open discussion but was soon dominated by one issue: data center staffing. The members’ concerns reflect the growing disquiet in the […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/04/SKILLS-SHORTAGE.jpg 976 2375 Sandra Vail https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Sandra Vail2019-05-22 09:00:482025-11-12 12:30:00The Data Center Staffing and Skills Shortage is here NOW!
Data Center Outage Severity Rating SystemUptime Institute, 2019

Comparing the severity of IT service outages: Uptime Institute’s Outage Severity Rating

May 8, 2019/in Design, Executive, Operations/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

Avoiding IT service outages is a big concern for any operator or service provider, especially one providing a business-critical service.  But when an outage does occur, the business impact can vary from “barely noticeable” to “huge and expensive.”  Anticipating and modeling the impact of a service interruption should be a part of incident planning and is key […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/04/Outage-red-image.jpg 520 1371 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2019-05-08 09:00:322025-11-12 12:32:12Comparing the severity of IT service outages: Uptime Institute’s Outage Severity Rating

“Think Globally, Act Locally”: Re-Evaluating Data Center Resiliency in the Face of Climate Change

January 16, 2019/in Design, Executive, Operations/by Kevin Heslin

The 1970s-era environmental phrase “Think globally, act locally,” is an apt way for data center operators to consider the best approach to understand and address the effects of climate change on their facilities and IT operations TODAY. Globally, we all hear that climate change threatens to bring warmer temperatures, stronger storms, rising sea levels, and […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2019/01/Flooding-Hurricane-ClimateChange-851x360.jpg 390 851 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2019-01-16 15:13:322019-01-16 15:13:32“Think Globally, Act Locally”: Re-Evaluating Data Center Resiliency in the Face of Climate Change

NEXTDC: Obsessed with the details so our customers’ business is always available

September 27, 2018/in Design, Executive, Operations/by Brett Ridley

This is a guest post written by Brett Ridley, Head of Central Operations and Facility Management for NEXTDC.NEXTDC is Australia’s leading independent data centre operator with a nationwide network of Uptime Institute certified Tier III and Tier IV facilities. NEXTDC provides enterprise-class colocation services to local and international organisations. If you are interested in participating in […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2018/09/NextDC-B2-night_851x360.jpg 360 851 Brett Ridley https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Brett Ridley2018-09-27 13:58:492019-04-22 10:54:43NEXTDC: Obsessed with the details so our customers’ business is always available
Fiber Optic Cables in Data Center

Application Resiliency vs. Infrastructure Resiliency

August 14, 2018/in Design, Executive/by Todd Traver

Software enabled application resiliency is now playing a significant and increasing role in bolstering applications availability and reliability across the enterprise, reducing risk to the business. No longer are clients solely reliant upon the stability provided by the electrical and mechanical systems in their data center. By utilizing new software techniques, enterprises are now able […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2018/08/uptime_institute_fiber_optic_network_resiliency.jpg 360 851 Todd Traver https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Todd Traver2018-08-14 15:56:122018-08-14 15:56:57Application Resiliency vs. Infrastructure Resiliency

Myths and Misconceptions Regarding the Uptime Institute’s Tier Certification System

July 20, 2017/in Design, Executive/by Kevin Heslin

True or false? When it comes to Tier Certification, just ask Uptime Institute By Uptime Institute Staff Uptime Institute’s Tier Classification System for data centers has reached the two-decade mark. Since its creation in the mid-1990s, Tiers has evolved from a shared industry terminology into the global standard for third-party validation of data center critical […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2017/07/tiers.jpg 594 1500 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2017-07-20 12:33:222017-07-20 12:33:22Myths and Misconceptions Regarding the Uptime Institute’s Tier Certification System

Luxembourg Colo Provides Multi-Tier Options

February 24, 2017/in Design, Executive/by Kevin Heslin

Luxconnect obtains different Tier Certifications to meet the needs of the changing market demands By Christine De Ridder LuxConnect, a multi-tenant, multi-tier data center and dark fiber network operator based in Luxembourg, developed an innovative strategy using Uptime Institute Tiers to differentiate the services and pricing it offers to key customer groups. In doing so, […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2017/02/UI1.jpg 594 1500 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2017-02-24 09:49:512017-03-02 12:25:27Luxembourg Colo Provides Multi-Tier Options

Moscow State University Meets HPC Demands

January 29, 2016/in Design/by Kevin Heslin

HPC supercomputing and traditional enterprise IT facilities operate very differently By Andrey Brechalov In recent years, the need to solve complex problems in science, education, and industry, including the fields of meteorology, ecology, mining, engineering, and others, has added to the demand for high-performance computing (HPC). The result is the rapid development of HPC systems, […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2016/01/moscow.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2016-01-29 08:57:492016-01-29 08:57:49Moscow State University Meets HPC Demands

Economizers in Tier Certified Data Centers

January 3, 2016/in Design/by Kevin Heslin

Achieving the efficiency and cost savings benefits of economizers without compromising Tier level objectives By Keith Klesner In their efforts to achieve lower energy use and greater mechanical efficiency, data center owners and operators are increasingly willing to consider and try economizers. At the same time, many new vendor solutions are coming to market. In […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/12/klesner.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2016-01-03 10:15:262016-01-04 08:34:30Economizers in Tier Certified Data Centers

Unipol Takes Space Planning to a New Level

October 28, 2015/in Design/by Kevin Heslin

Municipal requirements imposed difficult space considerations for Italian insurance company’s Tier IV data center By Andrea Ambrosi and Roberto Del Nero Space planning is often the key to a successful data center project. Organizing a facility into functional blocks is a fundamental way to limit interference between systems, reduce any problem related to power distribution, […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/10/Unipol.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-10-28 13:08:132015-10-28 13:08:13Unipol Takes Space Planning to a New Level

Australian Colo Provider Achieves High Reliability Using Innovative Techniques

September 22, 2015/in Design/by Kevin Heslin

NEXTDC deploys new isolated parallel diesel rotary uninterruptible
 power supply systems and other innovative technologies By Jeffrey Van Zetten NEXTDC’s colocation data centers in Australia incorporate innovation in engineering design, equipment selection, commissioning, testing, and operation. This quality-first philosophy saw NEXTDC become one of 15 organizations globally to win a 2015 Brill Award for Efficient IT. […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/09/NextDC.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-09-22 11:49:232015-09-22 11:49:23Australian Colo Provider Achieves High Reliability Using Innovative Techniques

Switzerland’s First Tier IV Certified Facility Achieves Energy Efficiency

September 14, 2015/in Design/by Kevin Heslin

Telecommunications company Swisscom AG builds a new data center in Berne, one of seven Tier IV data centers in Europe By Beat Lauber, Urs Moell, and Rudolf Anker Swisscom AG, a Switzerland-based telecommunications company, recently built a new data center in Berne, Switzerland. Swisscom spent three years and invested around US$62.5 million to build a […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/09/swisscom.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-09-14 13:47:022015-09-21 13:28:08Switzerland’s First Tier IV Certified Facility Achieves Energy Efficiency

LG CNS Deploys Custom Cooling  Approach in Korean Data Centers

September 2, 2015/in Design/by Kevin Heslin

IT services provider develops innovative cooling system for use in its own cloud computing data centers By Jong Wan Kim LG CNS is a major IT services and solutions provider in Korea. Since 1987, LG CNS has acted as the CIO for LG Group’s affiliates. As of the end of 2014, its data centers provided […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/08/LG.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-09-02 08:34:082015-09-02 08:34:08LG CNS Deploys Custom Cooling  Approach in Korean Data Centers

U.S. Bank Upgrades Its Data Center Electrical Distribution

August 14, 2015/in Design/by Kevin Heslin

Open heart surgery on the data center: Switchgear replacement in a live facility By Mark Johns U.S. Bank emerged during the 1990s from mergers and acquisitions among several major regional banks in the West and Midwest. Since then, the company continued to grow through additional large acquisitions and mergers with more than 50 banks. Today, […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/08/johns.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-08-14 08:38:332015-08-14 08:38:33U.S. Bank Upgrades Its Data Center Electrical Distribution

A Look at Data Center Cooling Technologies

July 30, 2015/in Design/by Kevin Heslin

Sabey optimizes air-cooled data centers through containment By John Sasser The sole purpose of data center cooling technology is to maintain environmental conditions suitable for information technology equipment (ITE) operation. Achieving this goal requires removing the heat produced by the ITE and transferring that heat to some heat sink. In most data centers, the operators […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/07/sasser.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-07-30 09:52:132015-07-30 09:52:13A Look at Data Center Cooling Technologies

Avoiding Data Center Construction Problems

May 13, 2015/in Design, Executive/by Kevin Heslin

Experience, teamwork, and third-party verification are keys to avoiding data center construction problems By Keith Klesner In 2014, Uptime Institute spoke to the common conflicts between data center owners and designers. In our paper, “Resolving Conflicts Between Data Center Owners and Designers” [The Uptime Institute Journal, Volume 3, p 111], we noted that both the […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/05/KlesnerTop.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-05-13 13:42:102015-05-13 14:29:11Avoiding Data Center Construction Problems

Improve Project Success Through Mission Critical Commissioning

May 4, 2015/in Design, Executive/by Kevin Heslin

Rigorous testing of data center components should be a continuous process By Ryan Orr, with Chris Brown and Ed Rafter Many data center owners and others commonly believe that commissioning takes place only in the last few days before the facility enters into operation. In reality, data center commissioning is a continuous process that, when […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/04/orr.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-05-04 07:30:482015-05-04 07:30:48Improve Project Success Through Mission Critical Commissioning

Case Study: Italy’s First Tier IV TCCF

April 24, 2015/in Design/by Kevin Heslin

System efficiency proves more important than equipment efficiency By Paolo Barberis, Leonardo Sergardi, and Ferdinando Ciardullo FastWeb is an Italian telecommunications operator, 100% owned by Swisscom, providing ultrabroadband services to the Italian consumer and corporate markets, in which it holds a 35% market share. Since its founding 15 years ago, FastWeb has invested in infrastructure. […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/04/fastwebtop.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-04-24 10:22:512015-04-24 12:15:34Case Study: Italy’s First Tier IV TCCF

Data center design goals and certification of proven achievement are not the same

March 17, 2015/in Design, Executive, Operations/by Matt Stansberry

On March 13, 2015, Data Center Knowledge published an article “ViaWest Accused of Misleading Customers in Las Vegas”. The following is excerpted from the article. ViaWest, the Shaw Communications-owned data center service provider, is being accused of misleading customers about reliability of its Las Vegas data center. Nevada Attorney General Adam Laxalt’s office has asked […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/03/1.jpg 475 1201 Matt Stansberry https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Matt Stansberry2015-03-17 11:56:222015-03-17 12:43:12Data center design goals and certification of proven achievement are not the same

Sun Life Plots Data Center Facilities and Operations Roadmap to Meet Application Demands

February 3, 2015/in Design, Operations/by Kevin Heslin

An imminent return of service causes a top-to-bottom examination of data center facilities and operations By Rocco Alonzi and Paolo Piro When Sun Life Financial completed a return of service for its data center operations in 2011, the Enterprise Infrastructure (IE) and Corporate Real Estate (CRE) teams immediately saw an opportunity to improve service stability, […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/02/sunlife7.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-02-03 09:46:082015-02-11 14:16:59Sun Life Plots Data Center Facilities and Operations Roadmap to Meet Application Demands

Improving Performance in Ever-Changing Mission-Critical IT Infrastructures

January 12, 2015/in Design/by Kevin Heslin

CenturyLink incorporates lessons learned and best practices for high reliability and energy efficiency. By Alan Lachapelle CenturyLink Technology Solutions and its antecedents (Exodus, Cable and Wireless, Qwest, and Savvis) have a long tradition of building mission critical data centers. With the advent of its Internet Data Centers in the mid-1990s, Exodus broke new ground by […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/01/cl.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-01-12 13:03:012015-01-12 13:03:01Improving Performance in Ever-Changing Mission-Critical IT Infrastructures

Operational Upgrade Helps Fuel Oil Exploration Surveyor

January 5, 2015/in Design/by Kevin Heslin

Petroleum Geo-Services increases its capabilities using innovative data center design By Rob Elder and Mike Turff Petroleum Geo-Services (PGS) is a leading oil exploration surveyor that helps oil companies find offshore oil and gas reserves. Its range of seismic and electromagnetic services, data acquisition, processing, reservoir analysis/interpretation, and multi-client library data all require PGS to […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2015/01/pgs.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2015-01-05 08:23:572015-01-05 08:23:57Operational Upgrade Helps Fuel Oil Exploration Surveyor

Thinking Ahead Can Prevent the Mid-Life Energy Crisis in Data Centers

December 5, 2014/in Design/by Kevin Heslin

Turning back the clock at Barclays Americas’ data centers By Jan van Halem and Frances Cabrera Barclays is a major global financial services provider engaged in personal banking, credit cards, corporate and investment banking, and wealth and investment management with an extensive international presence in Europe, the Americas, Africa, and Asia. Barclays has two major […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/12/barclays.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-12-05 12:56:552014-12-05 12:56:55Thinking Ahead Can Prevent the Mid-Life Energy Crisis in Data Centers

Close Coupled Cooling and Reliability

November 26, 2014/in Design/by Kevin Heslin

Achieving Concurrently Maintainable and Fault Tolerant cooling using various close coupled cooling technologies By Matt Mescall Early mainframe computers were cooled by water at the chip level. Then, as computing moved to the distributed server model, air replaced water. Typically, data centers included perimeter computer room air condition (CRAC) units to supply cold air to […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/11/19.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-11-26 12:17:192014-12-23 13:45:36Close Coupled Cooling and Reliability

Annual Data Center Industry Survey 2014

November 21, 2014/in Design, Executive, Operations/by Kevin Heslin

The fourth annual Uptime Institute Data Center Industry Survey provides an overview of global industry trends by surveying 1,000 data center operators and IT practitioners. Uptime Institute collected responses via email February through April 2014 and presented preliminary results in May 2014 at the 9th Uptime Institute Symposium: Empowering the Data Center Professional. To immediately […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/11/17-header.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-11-21 15:56:262015-07-24 08:54:12Annual Data Center Industry Survey 2014

Cogeneration powers South Africa’s first Tier III Certified data center

November 7, 2014/in Design/by Kevin Heslin

MTN’s new facility makes use of Kyoto Wheel By Olu Soluade, Robin Sloan, Willem Weber, and Philip Young MTN’s new data center in Centurion, Johannesburg, South Africa, includes a 500-square-meter (m2) space to support MTN’s existing Pretoria Switch. MTN provides cellular telecommunications services, hosted data space, and operations offices via a network of regional switches. […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/11/MTN-cover-image.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-11-07 14:36:182014-11-07 14:36:18Cogeneration powers South Africa’s first Tier III Certified data center

Russia’s First Tier IV Certification of Design Documents

November 6, 2014/in Design/by Kevin Heslin

Next Step: Preparing for Facility Certification By Alexey Karpov Mordovia Republic-Technopark Mordovia Data Center (Technopark Data Center) is one of the most significant projects in Mordovia (see Figure 1). The facility is a mini-city that includes research organizations, industry facilities, business centers, exhibition centers, schools, a residential village, and service facilities. One of the key […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/11/Technopark-cover.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-11-06 08:14:192014-11-06 08:14:19Russia’s First Tier IV Certification of Design Documents

TELUS SIDCs provide support to widespread Canadian network

September 8, 2014/in Design/by Kevin Heslin

TELUS SIDCs provide support to widespread Canadian network. SIDCs showcase best-in-class innovation and efficiency By Pete Hegarty TELUS built two Super Internet Data Center (SIDC) facilities as part of an initiative to help its customers reap the benefits of flexible, reliable, and secure IT and communication solutions. These SIDCs, located in Rimouski, Quebec, and Kamloops, […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/09/18.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-09-08 09:57:582014-09-08 09:57:58TELUS SIDCs provide support to widespread Canadian network
emert-cover-photo

Data Center Facility Owners See Modules as Efficient Way to Deploy Capital

September 4, 2014/in Design/by Kevin Heslin

Compass sets the course with new modular data center approach. The term modular has been used to describe a variety of approaches to data center design. Historically, the first commercially available modular design was a 2007 Sun Microsystems container-based product called the Black Box. Today, the term describes products that range from shipping containers and […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/09/emert-cover-photo.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-09-04 07:57:362014-09-04 08:41:19Data Center Facility Owners See Modules as Efficient Way to Deploy Capital
Data-center-owners-v-designers

Resolving Conflicts between Data Center Owners and Designers

August 7, 2014/in Design, Executive/by Kevin Heslin

Improving communication between the enterprise and design engineers during a capital project For over 10 years, Uptime Institute has sought to improve the relationship between data center design engineers and data center owners. Yet, it is clear that issues remain. Uptime Institute’s uniquely unbiased position—it does not design, construct, commission, operate, or provision equipment to […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/08/Data-center-owners-v-designers.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-08-07 13:06:172015-02-06 13:06:39Resolving Conflicts between Data Center Owners and Designers

Lessons Learned from the Tier Certification of an Operational Data Center

July 24, 2014/in Design/by Kevin Heslin

Telecom company Entel achieves first two Tier III Certification of Constructed Facility Awards in Chile Empresa Nacional de Telecomunicaciones S.A. (Entel) is the largest telecommunications company in Chile. The company reported US$3.03 billion in annual revenue in December 2012, and an EBITDA around 40%. In Chile, Entel holds a leading position in traditional data services, […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/07/Entel.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-07-24 09:30:442016-06-02 06:50:23Lessons Learned from the Tier Certification of an Operational Data Center

ATD Perspectives From Mainframes to Modular Designs

July 23, 2014/in Design/by Kevin Heslin

The experiences of Christopher Johnston, Elie Siam, and Dennis Julian are very different. Yet, their experiences as Accredited Tier Designers (ATDs) all highlight the pace of change in the industry. Somehow, though, despite significant changes in how IT services are delivered and business practices affect design, the challenge of meeting reliability goals remains very much […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/07/julian.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-07-23 08:16:032014-07-23 08:16:03ATD Perspectives From Mainframes to Modular Designs

ATD Interview: Elie Siam, Pierre Dammous & Partners

July 3, 2014/in Design/by Kevin Heslin

Industry Perspective: Three Accredited Tier Designers (ATDs) discuss 25 years of data center evolution The experiences of Christopher Johnston, Elie Siam, and Dennis Julian are very different. Yet, their experiences as Accredited Tier Designers (ATDs) all highlight the pace of change in the industry. Somehow, though, despite significant changes in how IT services are delivered […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/07/elie.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-07-03 05:47:312014-07-10 12:15:07ATD Interview: Elie Siam, Pierre Dammous & Partners

ATD Interview: Christopher Johnston, Syska Hennessy

June 18, 2014/in Design/by Kevin Heslin

Industry Perspective: Three Accredited Tier Designers discuss 25 years of data center evolution The experiences of Christopher Johnston, Elie Siam, and Dennis Julian are very different. Yet, their experiences as Accredited Tier Designers (ATDs) all highlight the pace of change in the industry. Somehow, though, despite significant changes in how IT services are delivered and […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/06/johnston.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-06-18 10:26:292014-06-19 07:10:42ATD Interview: Christopher Johnston, Syska Hennessy

Fuel System Design and Reliability

June 18, 2014/in Design/by Kevin Heslin

Topology and operational sustainability considerations must drive fuel system design. When Superstorm Sandy hit the Northeastern U.S., some data center owners and operators discovered that they hadn’t considered and treated their fuel systems as part of a mission-critical system. In one highly publicized story, a data center operator in New York City was forced to use a […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/06/keithmain2.jpg 475 1201 Kevin Heslin https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Kevin Heslin2014-06-18 10:22:442014-06-19 07:10:06Fuel System Design and Reliability

Accredited Tier Designer Profiles: Adel Rizk, Gerard Thibault and Michael Kalny

May 12, 2014/in Design/by Matt Stansberry

Three data center design professionals talk about their work and Uptime Institute’s ATD program. By Kevin Heslin, Uptime Institute Uptime Institute’s Accredited Tier Designer (ATD) program and its Tier Certification program have affected data center design around the world, raised standards for construction, and brought a new level of sophistication to facility owners, operators, and […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/05/26.jpg 475 1201 Matt Stansberry https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Matt Stansberry2014-05-12 11:48:212017-02-06 08:52:06Accredited Tier Designer Profiles: Adel Rizk, Gerard Thibault and Michael Kalny

Meeting Data Center Design Challenges in Santiago, Chile

May 8, 2014/in Design/by Matt Stansberry

Uptime Institute Accredited Tier Designers address particulates and seismic activity in the Chilean capitol. By Panagiotis Laziridis, ATD and Jan Carlos Sens, ATD The city of Santiago, Chile, is a challenging place to site a data center. It has a history of strong earthquakes, it is close to dozens of active volcanoes, and the nearby […]

Read more
https://journal.uptimeinstitute.com/wp-content/uploads/2014/05/30.jpg 475 1201 Matt Stansberry https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Matt Stansberry2014-05-08 12:12:552014-06-19 07:10:55Meeting Data Center Design Challenges in Santiago, Chile

Share this:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on LinkedIn (Opens in new window) LinkedIn
  • Share on Reddit (Opens in new window) Reddit
  • Share on WhatsApp (Opens in new window) WhatsApp
  • Email a link to a friend (Opens in new window) Email

Content Categories

  • Journal Home
  • Executive
  • Operations
  • Design

Subscribe to Journal via Email

Enter your email address to subscribe to Uptime Institute Journal and receive notifications of new articles by email.

  • Recent

Tags

Accredited Tier Designer (9) AI (21) artificial intelligence (16) ATD (10) Carbon Emissions (7) Climate Change (13) Cloud (22) Cloud Computing (17) Cloud Costs (15) Cloud Infrastructure (29) Cloud Migration (8) Colocation (6) cooling (9) Data Center (252) Data Center Availability (40) Data Center Cooling (13) Data Center Design (45) Data Center Disaster Recovery (7) Data Center Energy Efficiency (34) Data Center Facilities Management (43) Data Center Operations (66) data center power (8) Data Center Staffing (18) DCIM (9) digital Infrastructure (117) energy (8) Energy Efficiency (38) Environmental Sustainability (18) IT (7) IT Efficiency (16) IT Outages (10) M&O (6) outages (11) Public Cloud (7) PUE (10) Regulations (24) Resiliency (9) security (7) Sustainability (34) Sustainability Reporting (7) Tier Certification (26) Tier Certification Constructed Facility (16) Uptime Institute FORCSS (6) Uptime Institute Network (13) Uptime Institute Symposium (6)
© 2014-2025 Uptime Institute, LLC All rights reserved.
  • Link to X
  • Link to LinkedIn
  • Link to Mail
Scroll to top Scroll to top Scroll to top