• Link to X
  • Link to LinkedIn
  • Link to Mail
  • ABOUT UI
    • Business Partners
    • Careers
    • Contact Us
    • News & Press
    • Our Team
    • Press Releases
    • Branding Guidelines
  • CONTACT
Uptime Institute Blog
  • Journal
    • Journal Home
    • Executive
    • Operations
    • Design
  • AI Services
    • AI Infrastructure Advisory
  • Tier Certification
    • Overview
    • Design
    • Construction
    • Operations
    • Tier Gap Analysis
    • Prefabricated/Modular
    • Tier Certifications List
  • Professional Services
    • Overview
    • Infrastructure Services
    • Management and Operations Services
    • Energy and Sustainability Services
    • Consulting Services
  • Education
    • Education Framework
    • Course Calendar
    • Competency & Confidence Assessments
    • Private Education
    • Graduate Roster
  • Events
    • Industry Events
    • Leadership Events
    • Network Events
  • Network
    • Overview
    • Network Calendar
    • Network Roster
    • Request Corporate Access
    • Request Guest Access
    • Uptime Network Portal
  • Intelligence
  • Clients
    • Client Stories
  • Resources
    • Data Center Industry Surveys
    • Ebooks
    • Journal Blog
    • Product Datasheets
    • Research & Reports
    • Tier Specification Documents
    • Tools
    • Webinars
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu
Blog - Latest News
Crypto mines are turning into AI factories

Crypto mines are turning into AI factories

October 22, 2025/in Design, Executive, Operations/by Max Smolaks, Research Analyst, [email protected]

The pursuit of training ever-larger generative AI models has necessitated the creation of a new class of specialized data centers — facilities that have more in common with high-performance computing (HPC) environments than traditional enterprise IT.

These data centers support very high rack densities (130 kW and above with current Nvidia rack-scale systems), direct-to-chip liquid cooling, and supersized power distribution components. This equipment is deployed at scale, in facilities that consume tens of megawatts. Delivering such dense infrastructure at this scale is not just technically complicated — it often requires doing things that have never been attempted before.

Some of these ultra-dense AI training data centers are being built by well-established cloud providers and their partners — wholesale colocation companies. However, the new class of facility has also attracted a different kind of data center developer: former cryptocurrency miners. Many of the organizations now involved in AI infrastructure — such as Applied Digital, Core Scientific, CoreWeave, Crusoe and IREN — originated as crypto mining ventures.

Some have transformed into neoclouds, leasing GPUs at competitive prices. Others operate as wholesale colocation providers, building specialized facilities for hyperscalers, neoclouds, or large AI model developers like OpenAI or Anthropic. Few of them operated traditional data centers before 2020. These operators represent a significant and recent addition to the data center industry — especially in the US.

A league of their own

Crypto mining facilities differ considerably from traditional data centers. Their primary objective is to house basic servers equipped with either GPUs or ASICs (application-specific integrated circuits), running at near 100% utilization around the clock to process calculations that yield cryptocurrency tokens. The penalties for outages are direct — fewer tokens mean lower profits — but the hardware is generally considered disposable. The business case is driven almost entirely by the cost of power, which accounts for almost all of the operating expenditure.

Many crypto mines do not use traditional server racks. Most lack redundancy in power distribution and cooling equipment, and they have no means of continuing operations in the event of a grid outage: no UPS, no batteries, no generators, no fuel. In some cases, mining equipment is located outdoors, shielded from the rain, but little else.

While crypto miners didn’t build traditional data center facilities, they did have two crucial assets: land zoned for industrial use and access to abundant, low-cost power.

Around 2020, some of the largest crypto mining operators began pivoting toward hosting hardware for AI workloads — a shift that became more pronounced following the launch of ChatGPT in late 2022. Table 1 shows how quickly some of these companies have scaled their AI/HPC operations.

Table 1 The transformation of crypto miners

Table: The transformation of crypto miners

To develop data center designs that can accommodate the extreme power and cooling requirements of cutting-edge AI hardware, these companies are turning to engineers and consultants with experience in hyperscale projects. The same applies to construction companies. The resulting facilities are built to industry standards and are concurrently maintainable.

There are three primary reasons why crypto miners were successful in capitalizing on the demand for high-density AI infrastructure:

  • These organizations were accustomed to moving quickly, having been born in an industry that had to respond to volatile cryptocurrency pricing, shifting regulations and fast-evolving mining hardware.
  • Many were already familiar with GPUs through their use in crypto mining — and some had begun renting them out for research or rendering workloads.
  • Their site selection was primarily driven by power availability and cost, rather than proximity to customers or network hubs.

Violence of action

Applied Digital, a publicly traded crypto mining operator based in North Dakota, presents an interesting case study. The state is one of the least developed data center markets in the US, with only a few dozen facilities in total.

Applied Digital’s campus in Ellendale was established to capitalize on cheap renewable power flowing between local wind farms and Chicago. In 2024, the company removed all mentions of cryptocurrency from its website — despite retaining sizable (100 MW-plus) mining operations. It then announced plans to build a 250 MW AI campus in Ellendale, codenamed Polaris Forge, to be leased by CoreWeave.

The operator expects the first 100 MW data center to be ready for service in late 2025. The facility will use direct liquid cooling and is designed to support 300 kW-plus rack densities. It is built to be concurrently maintainable, powered by two utility feeds, and will feature N+2 redundancy on most mechanical equipment. To ensure cooling delivery in the event of a power outage, the facility will be equipped with 360,000 gallons (1.36 million liters) of chilled water thermal storage. This will be Applied Digital’s first non-crypto facility.

The second building, with a capacity of 150 MW, is expected to be ready in the middle of 2026. It will deploy medium-voltage static UPS systems to improve power distribution efficiency and optimize site layout. The company has several more sites under development.

Impact on the sector

Do crypto miners have an edge in data center development? What they do have is existing access to power and a higher tolerance for technical and business risk — qualities that enable them to move faster than much of the traditional competition. This willingness to place bets matters in a market that is lacking solid fundamentals: in 2025, capital expenditure on AI infrastructure is outpacing revenue from AI-based products by orders of magnitude. The future of generative AI is still uncertain.

At present, this new category of data center operators appears to be focusing exclusively on the ultra-high-density end of the market and is not competing for traditional colocation customers. For now, they don’t need to either, as demand for AI training capacity alone keeps them busy. Still, their presence in the market introduces a new competitive threat to colocation providers that have opted to accommodate extreme densities in their recently built or upcoming facilities.

M&E and IT equipment suppliers have welcomed the new arrivals — not simply because they drive overall demand but because they are new buyers in a market increasingly dominated by a handful of technology behemoths. Some operators will be concerned about supply chain capacity, especially when it comes to large-scale projects: high-density campuses could deplete the stock of data center equipment such as large generators, UPS systems and transformers.

One of the challenges facing this new category of operators is the evolving nature of AI hardware. Nvidia, for example, intends to start shipping systems that consume more than 500 kW per compute rack by the end of 2027. It is not clear how many data centers being built today will be able to accommodate this level of density.


The Uptime Intelligence View

The simultaneous pivot by several businesses toward building much more complex facilities is peculiar, yet their arrival will not immediately affect most operators.

While this trend will create business opportunities for a broad swathe of design, consulting and engineering firms, it is also likely to have a negative impact on equipment supply chains, extending lead times for especially large-capacity units.

Much of this group’s future success hinges on the success of generative AI in general — and the largest and most compute-hungry models in particular — as a tool for business. However, the facilities they are building are legitimate data centers that will remain valuable even if the infrastructure needs of generative AI are being overestimated.

Share this:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on LinkedIn (Opens in new window) LinkedIn
  • Share on Reddit (Opens in new window) Reddit
  • Share on WhatsApp (Opens in new window) WhatsApp
  • Email a link to a friend (Opens in new window) Email
Tags: AI, artificial intelligence, Crypto, Data Center, digital Infrastructure
https://journal.uptimeinstitute.com/wp-content/uploads/2025/10/Crypto-mines-are-turning-into-AI-factories-featured.jpg 540 1030 Max Smolaks, Research Analyst, [email protected] https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Max Smolaks, Research Analyst, [email protected]2025-10-22 15:00:002025-10-20 16:20:24Crypto mines are turning into AI factories
You might also like
Long shifts in data centers — time to reconsider? Long shifts in data centers — time to reconsider?
Lithium-Ion Batteries in the Data Center2019 Lithium Ion Batteries for the data center. Are they ready for production yet?
Data center operators ponder the nuclear option Data center operators ponder the nuclear option
The ultimate liquid cooling: heat rejection into water The ultimate liquid cooling: heat rejection into water
Survey findings link higher redundancy to lower outage risk Survey findings link higher redundancy to lower outage risk
AI and cooling: toward more automation AI and cooling: toward more automation
A Look at Data Center Cooling Technologies
Pandemics: Operators plan to be ready next time

Content Categories

  • Journal Home
  • Executive
  • Operations
  • Design

Subscribe to Journal via Email

Enter your email address to subscribe to Uptime Institute Journal and receive notifications of new articles by email.

  • Recent

Tags

Accredited Tier Designer (9) AI (24) artificial intelligence (19) ATD (10) Carbon Emissions (7) Climate Change (13) Cloud (23) Cloud Computing (17) Cloud Costs (15) Cloud Infrastructure (29) Cloud Migration (8) Colocation (7) cooling (13) Data Center (261) Data Center Availability (40) Data Center Cooling (13) Data Center Design (45) Data Center Disaster Recovery (7) Data Center Energy Efficiency (34) Data Center Facilities Management (43) Data Center Operations (67) data center power (9) Data Center Staffing (19) DCIM (9) digital Infrastructure (126) energy (8) Energy Efficiency (38) Environmental Sustainability (18) IT (7) IT Efficiency (17) IT Outages (10) M&O (6) outages (12) Public Cloud (7) PUE (10) Regulations (25) Resiliency (9) security (7) Sustainability (34) Sustainability Reporting (7) Tier Certification (26) Tier Certification Constructed Facility (16) Uptime Institute FORCSS (6) Uptime Institute Network (13) Uptime Institute Symposium (6)
© 2014-2025 Uptime Institute, LLC All rights reserved.
  • Link to X
  • Link to LinkedIn
  • Link to Mail
Link to: Cybersecurity and the cost of human error Link to: Cybersecurity and the cost of human error Cybersecurity and the cost of human errorCybersecurity and the cost of human error Link to: Is this the data center metric for the 2030s? Link to: Is this the data center metric for the 2030s? Is this the data center metric for the 2030s?Is this the data center metric for the 2030s?