PUE: The golden metric is looking rusty
When the PUE (power usage effectiveness) metric was first discussed at a meeting of The Green Grid in Santa Clara, back in 2007, a microphone stand was placed in each aisle of the auditorium. The importance of the initiative was understood even then: experts, including the founders of Uptime Institute, formed lines to give their considered input. And if there was one point that came across, it was that the industry should not treat PUE as a comparative metric, a gold standard that every designer, operator and planning authority must chase down, for comparison, presentation and applause.
Thirteen years on, that is almost exactly what has happened. PUE, thanks to its simplicity and universal applicability, has become the critical benchmark for scoring data centers for efficiency and “greenness” (environmental responsibility). But it is often used uncritically.
This has had both positive and negative consequences. The positive side is that PUE values have been forced down across the world, as operators strive to reduce waste and operating costs. To meet their goals, suppliers have focused on improving electrical efficiency of equipment and have developed nonmechanical alternatives (such as free cooling). PUEs have fallen from an average of 2.5 in 2007 to around 1.6 today. In an Uptime Institute survey, around 95% of respondents said it is important that colocation companies have a low PUE.
So what is the negative side? Its simplicity. The very quality that led to PUE’s near universal adoption also may have led to its being over-used and misapplied — increasingly, with unintended consequences.
This observation is hardly new — indeed, this is exactly what those experts feared back in 2007 as they lined up to voice their concerns. And it is why PUE was developed into a standard, with rules on how it should be measured, and why Partial PUE variants were developed.
But the unintended consequences are becoming more serious and more concerning. The metric may be driving the wrong behaviors. For this reason, it is very possible that PUE values may begin to be de-emphasized in the near future and more operators may allow their number to rise a little. (In 2019, Uptime Institute did note a marginal rise in PUE values.) If this happens, some operators may find themselves in conflict with certain regulators and planners, for whom PUE has been an easily understood but simplistic way of enforcing environmental goals (policing this is another matter). These planning authorities, then, may also need to review their policies around driving down the PUE numbers. (California, Singapore, Amsterdam, take note.)
There are, we think, three strong and strengthening reasons why focusing on the PUE of the data center might be counter-productive:
- Resiliency (N to N+1). There is an industry-wide move to increase the resiliency of data centers, with the growing dependency on IT and the impact of the pandemic and extreme weather among the drivers. At the physical site level, it is difficult to improve redundancy and resiliency without adding power-consuming equipment — which drives up the PUE. (Similarly, one operator installed the highest level of MERV [Minimum Efficiency Reporting Value] air filters to filter out viruses — but fan energy use rose by 8% and the PUE value rose accordingly.)
- Water use. The drive to improve energy efficiency has encouraged operators to use economizers and, in particular, adiabatic and evaporative cooling and chillers. But this has often involved a trade-off: energy use drops, but water use rises. That compromise is becoming problematic in some regions, where climate change means water is becoming more scarce and, in some instances, a bigger local environmental issue than on-site energy use. Again, PUE may be the wrong metric to track — WUE (water usage effectiveness) is a more important one.
- IT efficiency. It is widely known that while facilities have become ever more energy efficient, IT use can be extremely inefficient and wasteful, with processors and memory often drawing energy while doing relatively little work. Energy-saving efficiency investments on the IT side, however, are not rewarded with a lower PUE, but rather a higher one (as PUE is the ratio of the IT to non-IT energy figures). This has been known from the outset. With a slew of new technologies becoming available to lower the overall energy figure, it is important that the need to meet a given PUE value does not discourage investments and innovation on the IT side.
There is, to be fair, a good counter-argument to these three points: that by searching for ways to lower the PUE regardless of these constraints, data center operators can find ways to meet all the goals. Liquid cooling, for example, can be highly resilient and uses little water. The argument here, then, is not for anyone to abandon PUE, or to stop watching and measuring it, but to apply it more cautiously than ever, and more flexibly.

UI 2020
2020


UI 2020
Uptime Institute
UI 2020
UI 2020