• Link to X
  • Link to LinkedIn
  • Link to Mail
  • ABOUT UI
    • Business Partners
    • Careers
    • Contact Us
    • News & Press
    • Our Team
    • Press Releases
    • Branding Guidelines
  • CONTACT
Uptime Institute Blog
  • Journal
    • Journal Home
    • Executive
    • Operations
    • Design
  • AI Services
    • AI Infrastructure Advisory
  • Tier Certification
    • Overview
    • Design
    • Construction
    • Operations
    • Tier Gap Analysis
    • Prefabricated/Modular
    • Tier Certifications List
  • Professional Services
    • Overview
    • Infrastructure Services
    • Management and Operations Services
    • Energy and Sustainability Services
    • Consulting Services
  • Education
    • Education Framework
    • Course Calendar
    • Competency & Confidence Assessments
    • Private Education
    • Graduate Roster
  • Events
    • Industry Events
    • Leadership Events
    • Network Events
  • Network
    • Overview
    • Network Calendar
    • Network Roster
    • Request Corporate Access
    • Request Guest Access
    • Uptime Network Portal
  • Intelligence
  • Clients
    • Client Stories
  • Resources
    • Data Center Industry Surveys
    • Ebooks
    • Journal Blog
    • Product Datasheets
    • Research & Reports
    • Tier Specification Documents
    • Tools
    • Webinars
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu
Blog - Latest News
Retail vs wholesale: finding the right colo pricing model

Retail vs wholesale: finding the right colo pricing model

December 3, 2025/in Executive, Operations/by Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, [email protected]

Colocation providers may offer two pricing and packaging models to sell similar products and capabilities. In both models, customers purchase space, power and services. However, the method of purchase differs.

In a retail model, customers purchase a small quantity of space and power, usually by the rack or a fraction of a rack. The colocation provider standardizes contracts, pricing and capabilities — the cost and complexity of delivering to a customer’s precise requirements are not justified, considering the relatively small contract value.

In a wholesale model, customers purchase a significantly larger quantity of space and power, typically at least a dedicated, enclosed suite of white space. Due to the size of these contracts, colocation providers need to be flexible in meeting customer needs, even potentially building new facilities to accommodate their requirements. The colocation provider negotiates price and terms, and customers often prefer to pay for actual power consumption rather than be billed on maximum capacity. A metered model allows the customer to scale power usage in response to changing demands.

A colocation provider may focus on a particular market by offering only a retail or wholesale model, or the provider may offer both to broaden its appeal. The terms “wholesale” and “retail” colocation more accurately describe the pricing and packaging models used by colocation providers rather than the type of customer.

Table 1 Key differences between retail and wholesale colocation providers

Table: Key differences between retail and wholesale colocation providers

Retail colocation deals typically have higher gross margins in percentage terms, but the volume of sales is lower. Most colocation providers would rather sell wholesale contracts because they offer higher revenues through larger volumes of sales, despite having lower gross margins. As wholesale colocations are better prospects, retail customers are more likely to experience cost rises at renewal than wholesale customers.

Retail colocation pricing model

Retail terms are designed to be simple and predictable. Customers are typically charged a fixed fee based on the maximum power capacity supplied to equipment and the space used. This fee covers both the repayment of fixed costs, and the variable costs associated with IT power and cooling. The fixed fee bundles all these elements together, so customers have no visibility into these individual components — but they benefit from predictable pricing.

In retail colocation, the facilities are already available, so capital costs are recovered across all retail customers through standard pricing. If a customer exceeds their allotted maximum power capacity, they risk triggering a breaker and potentially powering down their IT equipment. Some colocation providers monitor for overages and warn customers that they need to increase their capacity before an outage occurs.

Customers are likely to purchase more power capacity than they need to prevent these outages. As a result, some colocation providers may deliberately oversubscribe power consumption to reduce their power costs and increase their profit margins. There are operational and reputational risks if oversubscription causes service degradation or outages.

Some colocation providers also meter power, charging a fee based on IT usage, which factors in the repayment of capital, IT and cooling costs, as well as a profit margin. Those with metering enabled may charge customers for usage exceeding maximum capacity, typically at a higher rate.

Can a colocation provider increase prices during a contract term? Occasionally, but only as a last resort — such as if power costs increase significantly. This possibility will be stipulated in the contract as an emergency or force majeure measure.

Usually, an internet connection is included. However, data transfer over that connection may be metered or bundled into a fixed cost package. Customers have the option to purchase cross-connects linking their infrastructure to third-party communications providers, including on-ramps to cloud providers.

Wholesale colocation pricing model

Wholesale colocation pricing is designed to offer customers the flexibility to utilize their capacity as they choose. Because terms are customized, pricing models will vary from customer to customer.

Some customers may prefer to pay for a fixed capacity of total power, regardless of whether the power is used or not. In this model, both IT power and cooling costs are factored into the price.

Other customers may prefer a more granular approach, with multiple charging components:

  • Fixed fee per unit of space/rack based on maximum power capacity and is designed to cover the colocation provider’s fixed costs, while including a profit margin.
  • Variable IT power costs are passed directly from the electricity supplier to the customer, metered in kilowatts (kW). Customers bear the full cost of price fluctuations, which can change rapidly depending on grid conditions.
  • To account for variable cooling costs, power costs may be calculated by multiplying actual power usage by an agreed design PUE to create an “additional power” fee. This figure may also be multiplied by a “utilization factor” to reflect cases where a customer is using only a small fraction of the data hall (and therefore impacting overall efficiency).

Some customers may prefer a blended model of both a fixed element for baseline capacity and a variable charge for consumption above the baseline. Redundant feeds are also likely to impact cost. If new data halls need to be constructed, these costs may be passed on to the customers directly, or some capital may be recovered through a higher fixed rack fee.

Alternatively, for long-term deployments, customers may opt for either a “build-to-suit” or “powered shell” arrangement. In a build-to-suit model, the colocation provider designs and constructs the facility —including power, cooling and layout — to the customer’s exact specifications. The space is then leased back to the customer, typically under a long-term agreement exceeding a decade.

In a powered shell setup, the provider delivers a completed exterior building with core infrastructure, such as utility power and network access. The customer is then responsible for outfitting the interior (racks, cooling, electrical systems) to suit their operational needs.

Most customers using wholesale colocation providers will need to implement cross-connects to third-party connectivity and network providers hosted in meet-me rooms. They may also need to arrange the construction of new capacity into the facility with the colocation provider and suppliers.

Hyperscalers are an excellent prospect for wholesale colocation, given their significant scale. However, their limited numbers and strong market power enable them to negotiate lower margins from colocation providers.

Table 2 Pricing models used in retail and wholesale colocation

Table: Pricing models used in retail and wholesale colocation

In a retail colocation engagement, the customer has limited negotiating power — with little scale, they generally have minimal flexibility on pricing, terms and customization. In a wholesale engagement, the opposite is true, and the arrangement favors the customer. Colocation providers want the scale and sales volume, so are willing to cut prices and accommodate additional requirements. They are also willing to offer flexible pricing in response to customers’ rapidly changing requirements.


The Uptime Intelligence View

Hyperscalers have the strongest market power to dictate contracts and prices. With so few players, it is unlikely that many hyperscalers will be bidding for the same space, which would push up prices. However, colocation providers still want their business, because of the volume it brings. They would prefer to reduce gross margins to ensure a win, rather than risk losing a customer with such unmatched scale.

Share this:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on LinkedIn (Opens in new window) LinkedIn
  • Share on Reddit (Opens in new window) Reddit
  • Share on WhatsApp (Opens in new window) WhatsApp
  • Email a link to a friend (Opens in new window) Email
Tags: Colocation, Data Center, digital Infrastructure, finance, hyperscale
https://journal.uptimeinstitute.com/wp-content/uploads/2025/12/Retail-vs-wholesale-right-colo-pricing-model-featured.jpg 540 1030 Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, [email protected] https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Dr. Owen Rogers, Senior Research Director for Cloud Computing, Uptime Institute, [email protected]2025-12-03 12:00:002025-12-03 09:52:17Retail vs wholesale: finding the right colo pricing model
You might also like
Data center operators cautiously support nuclear Data center operators cautiously support nuclear
Big Tech Regulation Big Tech Regulations: an UPSIDE for Cloud customers?
Business Outages Why do some industries and organizations suffer more serious, high profile outages than others?
LG CNS Deploys Custom Cooling  Approach in Korean Data Centers
Industry consensus on sustainability looks fragile Industry consensus on sustainability looks fragile
2020 Will the pandemic accelerate the move to public cloud?
UI @ 2021 The insider threat: Social engineering is raising security risks
Failure Doesn’t Keep Business Hours: 24×7 Coverage

Content Categories

  • Journal Home
  • Executive
  • Operations
  • Design

Subscribe to Journal via Email

Enter your email address to subscribe to Uptime Institute Journal and receive notifications of new articles by email.

  • Recent

Tags

Accredited Tier Designer (9) AI (24) artificial intelligence (19) ATD (10) Carbon Emissions (7) Climate Change (13) Cloud (23) Cloud Computing (17) Cloud Costs (15) Cloud Infrastructure (29) Cloud Migration (8) Colocation (7) cooling (13) Data Center (261) Data Center Availability (40) Data Center Cooling (13) Data Center Design (45) Data Center Disaster Recovery (7) Data Center Energy Efficiency (34) Data Center Facilities Management (43) Data Center Operations (67) data center power (9) Data Center Staffing (19) DCIM (9) digital Infrastructure (126) energy (8) Energy Efficiency (38) Environmental Sustainability (18) IT (7) IT Efficiency (17) IT Outages (10) M&O (6) outages (12) Public Cloud (7) PUE (10) Regulations (25) Resiliency (9) security (7) Sustainability (34) Sustainability Reporting (7) Tier Certification (26) Tier Certification Constructed Facility (16) Uptime Institute FORCSS (6) Uptime Institute Network (13) Uptime Institute Symposium (6)
© 2014-2025 Uptime Institute, LLC All rights reserved.
  • Link to X
  • Link to LinkedIn
  • Link to Mail
Link to: Electrical considerations with large AI compute Link to: Electrical considerations with large AI compute Electrical considerations with large AI computeElectrical considerations with large AI compute Link to: AI power fluctuations strain both budgets and hardware Link to: AI power fluctuations strain both budgets and hardware AI power fluctuations strain both budgets and hardwareAI power fluctuations strain both budgets and hardware
Scroll to top Scroll to top Scroll to top