• Link to X
  • Link to LinkedIn
  • Link to Mail
  • ABOUT UI
    • Business Partners
    • Careers
    • Contact Us
    • News & Press
    • Our Team
    • Press Releases
    • Branding Guidelines
  • CONTACT
Uptime Institute Blog
  • Journal
    • Journal Home
    • Executive
    • Operations
    • Design
  • AI Services
    • AI Infrastructure Advisory
  • Tier Certification
    • Overview
    • Design
    • Construction
    • Operations
    • Tier Gap Analysis
    • Prefabricated/Modular
    • Tier Certifications List
  • Professional Services
    • Overview
    • Infrastructure Services
    • Management and Operations Services
    • Energy and Sustainability Services
    • Consulting Services
  • Education
    • Education Framework
    • Course Calendar
    • Competency & Confidence Assessments
    • Private Education
    • Graduate Roster
  • Events
    • Industry Events
    • Leadership Events
    • Network Events
  • Network
    • Overview
    • Network Calendar
    • Network Roster
    • Request Corporate Access
    • Request Guest Access
    • Uptime Network Portal
  • Intelligence
  • Clients
    • Client Stories
  • Resources
    • Data Center Industry Surveys
    • Ebooks
    • Journal Blog
    • Product Datasheets
    • Research & Reports
    • Tier Specification Documents
    • Tools
    • Webinars
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu
Blog - Latest News
2020

Data Centers and Thunder, Lightning, Wind and Rain

September 28, 2020/in Design, Executive, Operations/by Chris Brown, Chief Technical Officer, Uptime Institute

Data centers are built and sited to withstand all that Mother Nature can throw at them — or at least, is likely to throw at them — during their lifecycle. This has long been a given, practiced and understood by designers, planners and regulators. But climate change is changing everything. Recent weather events have led some governmental agencies to ask how exposed data centers are from climate, such as high winds and lightning.

These are questions data centers throughout the world should consider, as storms and other natural disasters are increasingly frequent and severe. In the last few weeks alone, the world has experienced record-shattering derechos and tropical cyclones, as well as heatwaves and wildfires (both of which can alter wind patterns). Managers must review their data center’s resiliency and disaster recovery plans in the context of the amplifying effects of climate change. As we said in the Uptime Institute report A mission-critical industry unprepared for climate change, these reviews should be conducted regularly and plans updated; the climate is, regrettably, changing rapidly and proving volatile.

Recently, Uptime Institute was asked (via our colleagues at TechUK, a UK membership body for the IT industry) to give our views on three specific issues that might arise as a result of severe storms: staff access during storms, lightning strikes, and standards. Some thoughts on these are below.

The first relates to blocked transport routes — that is, how do data centers manage if staff are unable to get to work? The answer is, most data centers have a plan for this. This is an aspect of Uptime Institute’s Tier Standard: Operational Sustainability program, and it requires preparation and budget. When bad weather is forecast, many data centers either locate personnel at the facility or in hotels nearby. Because one shift cannot leave the site until they are relieved by the next shift, staff may work overtime waiting for the next crew to arrive. All these contingencies must be considered — possibly for extended periods of time. In extremis, of course, it is possible for staff to remain on site, with sleeping accommodation and food. But this is not a practice that is advised except in the most severe situations.

Another question asked after countermeasures against damage from lightning strikes and/or power surges. The answer first lies in local guidance and regulations. All locales are a bit different, but most have some life safety codes that address power surges and lightning. Lightning protection systems are foremost geared to building protection, but other codes cover ways to prevent local lightning strikes from impacting other systems, such as power and communication systems. Typically, data centers will not only meet these codes, but also exceed them in some ways.

There are ways to design the facility to help reduce the risk of the data center itself being affected. A first step is to incorporate a lightning protection system that uses grounded lightning rods or active systems to shunt ion buildup in the immediate atmosphere to ground. This stops the local buildup of a charge that will result in a lightning strike.

Another issue to anticipate is that a lightning strike can occur near the data center and could enter the facility via the power system. Electrical systems are often designed to transfer the energy from a lightning strike to a grounding device. The efficacy of this strategy depends on the proximity of a strike to the service entry. Outdoor communications cables (telecommunications or controls) usually have devices to block increased voltage from entering the facility.

In locations where lightning is prevalent, many facilities circumvent the problem: when a storm is forecast, they transfer to on-site power production and isolate from the outside power system altogether. This underlines the need for on-site power systems; because two utility feeders are installed in relatively close proximity to one another, a single strike could impact both systems. Dual utility feeds cannot provide the absolute isolation that on-site power production can.

A third question asked after standards that cover risks from lightning and/or high winds. Local building codes address this, but such codes are intended to help ensure human life is not put at risk during such events, not that a facility operates through it. Tier Standard: Operational Sustainability addresses this by requiring the site risks from natural events be addressed.

The challenges vary based on location and threat. In the US, Texas Tech University has done research on winds and tornadoes for over 20 years. They have an air cannon that shoots things like wooden boards at buildings to see how they perform. This research is used to help structural engineers learn how to harden structures against high wind and the debris it carries. The US Federal Emergency Management Agency has developed guidance on how to prepare for extreme weather events, as have other nations’ governments regarding threats their regions face.

There is one important thing to keep in mind: While people are quite capable of dealing with the typical or even slightly more severe than usual threats in their area, this does not mean a data center will necessarily be able to operate through it. Storms seem to be getting more severe; in August 2020, the US experienced the strongest hurricane (Hurricane Laura) ever to make landfall on the Texas Gulf Coast.

Even when storms diminish after landfall, they can do a lot of (sometimes unpredictable) damage. For example, just three years before Laura, Hurricane Harvey dumped so much rain that 500-year flood planes were inundated. This is not something most prepare for.

In such situations, even if the data center is operational, the telecommunications system may have facilities that are not. In these cases, a data center is ready to operate but can’t communicate with the outside world. And staff’s personal priorities also must be considered: few will report to work when their family’s safety is at risk — a lesson learned in several natural disasters.

Bottom Line: While we should take precautions to help ensure data centers are prepared for the foreseeable, we have to remember that just hardening a data center is not enough; Mother Nature will always show us where we stand in the grand scheme of things.

Share this:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on LinkedIn (Opens in new window) LinkedIn
  • Share on Reddit (Opens in new window) Reddit
  • Share on WhatsApp (Opens in new window) WhatsApp
  • Email a link to a friend (Opens in new window) Email
Tags: Data Center, Data Center Design
https://journal.uptimeinstitute.com/wp-content/uploads/2020/09/pexels-photo-1446076-blogsm.jpg 1165 3144 Chris Brown, Chief Technical Officer, Uptime Institute https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Chris Brown, Chief Technical Officer, Uptime Institute2020-09-28 06:00:522020-09-11 14:50:41Data Centers and Thunder, Lightning, Wind and Rain
You might also like
The Trend of PUE in 2019Uptime Institute Is PUE actually going UP?
DCIM past and present: what’s changed? DCIM past and present: what’s changed?
Consensus on regulatory goals hides national differences Consensus on regulatory goals hides national differences
UI 2020 Why ASHRAE is concerned about edge data centers
24x7 carbon-free energy (part two): getting to 100% 24×7 carbon-free energy (part two): getting to 100%
Data center operators cautiously support nuclear Data center operators cautiously support nuclear
OT protection: is air-gapping the answer? OT protection: is air-gapping the answer?
Russia’s First Tier IV Certification of Design Documents

Content Categories

  • Journal Home
  • Executive
  • Operations
  • Design

Subscribe to Journal via Email

Enter your email address to subscribe to Uptime Institute Journal and receive notifications of new articles by email.

  • Recent

Tags

Accredited Tier Designer (9) AI (24) artificial intelligence (19) ATD (10) Carbon Emissions (7) Climate Change (13) Cloud (23) Cloud Computing (17) Cloud Costs (15) Cloud Infrastructure (29) Cloud Migration (8) Colocation (7) cooling (13) Data Center (261) Data Center Availability (40) Data Center Cooling (13) Data Center Design (45) Data Center Disaster Recovery (7) Data Center Energy Efficiency (34) Data Center Facilities Management (43) Data Center Operations (67) data center power (9) Data Center Staffing (19) DCIM (9) digital Infrastructure (126) energy (8) Energy Efficiency (38) Environmental Sustainability (18) IT (7) IT Efficiency (17) IT Outages (10) M&O (6) outages (12) Public Cloud (7) PUE (10) Regulations (25) Resiliency (9) security (7) Sustainability (34) Sustainability Reporting (7) Tier Certification (26) Tier Certification Constructed Facility (16) Uptime Institute FORCSS (6) Uptime Institute Network (13) Uptime Institute Symposium (6)
© 2014-2025 Uptime Institute, LLC All rights reserved.
  • Link to X
  • Link to LinkedIn
  • Link to Mail
Link to: Will the pandemic accelerate the move to public cloud? Link to: Will the pandemic accelerate the move to public cloud? Will the pandemic accelerate the move to public cloud?2020 Link to: Infographic: Data Center Industry Staffing Shortage is Getting Worse Link to: Infographic: Data Center Industry Staffing Shortage is Getting Worse Staffing and Gender Diversity in the Data Center2020Infographic: Data Center Industry Staffing Shortage is Getting Worse
Scroll to top Scroll to top Scroll to top