• Link to X
  • Link to LinkedIn
  • Link to Mail
  • ABOUT UI
    • Business Partners
    • Careers
    • Contact Us
    • News & Press
    • Our Team
    • Press Releases
    • Branding Guidelines
  • CONTACT
Uptime Institute Blog
  • Journal
    • Journal Home
    • Executive
    • Operations
    • Design
  • AI Services
    • AI Infrastructure Advisory
    • AI Custom Support
  • Tier Certification
    • Overview
    • Design
    • Construction
    • Operations
    • Tier Gap Analysis
    • Prefabricated/Modular
    • Tier Certifications List
  • Professional Services
    • Overview
    • Infrastructure Services
    • Management and Operations Services
    • Energy and Sustainability Services
    • Consulting Services
  • Education
    • Course Details
    • Course Calendar
    • Competency & Confidence Assessments
    • Private Education
    • Graduate Roster
  • Events
    • Industry Events
    • Leadership Events
    • Network Events
  • Network
    • Overview
    • Network Calendar
    • Network Roster
    • Request Corporate Access
    • Request Guest Access
    • Uptime Network Portal
  • Intelligence
  • Clients
    • Client Stories
  • Resources
    • Data Center Industry Surveys
    • Ebooks
    • Journal Blog
    • Product Datasheets
    • Research & Reports
    • Tier Specification Documents
    • Tools
    • Webinars
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu
Blog - Latest News
2020

Which regions have the most energy efficient data centers?

August 24, 2020/in Design, Operations/by Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com

When the PUE (Power Usage Effectiveness) metric for data centers was first agreed upon by the members of The Green Grid back in 2007, almost everyone in that crowded room in California agreed: This is not intended to be used as comparative metric across sites (as every situation is different) but it would be an excellent metric when comparing the effect of improvements at any site over time.

It is with some wariness, then, that Uptime Institute publishes the chart below showing that, overall, Europe has the most energy efficient data centers, and the Middle East and Africa, the least efficient.

The data comes from a question Uptime asks each year as part of our global data center survey: What is the average annual PUE for your largest data center? Among the nearly 450 respondents to that question in 2020, the average PUE of their largest data center was 1.59. This number was down slightly from last year, but effectively continued a trend of no improvement, or marginal improvement, since 2013.

The chart is based on a subset of the data — those who reported PUEs between 1.0 and 2.19 (313 respondents). We considered others to be special cases or extreme outliers (see below). Regional averages ranged from a low of 1.46 (Europe) to 1.79 (Africa and the Middle East).



In the areas with the highest PUEs — Latin America, Africa, the Middle East and much of the Asia-Pacific region — climate may play a factor. Regions with less temperate environmental profiles may be less able to take advantage of free cooling technologies, which can substantially reduce power use. This is especially so in areas with high humidity or water constraints.

Other factors may cause operators to take an approach that is less energy efficient than they would like, but that is less risky. For example, operators in regions that are prone to supply chain issues, that lack reliable access to service technicians, or that are subject to power grid instability may hesitate to use techniques or technologies that save energy but may have a more narrow margin for error. They may opt for higher levels of redundancy, which, of course, require more power.

The two regions reporting the lowest PUEs — Europe and the US/Canada — have roughly equivalent sample sizes, but Europe’s average PUE is almost 5% lower. Why? This might be because European energy prices tend to be higher, and/or that the attitudes of operators and regulators are more environmentally conscientious than those in the US. Another contributing factor: London, Amsterdam and Frankfurt house a big portion of the European continent’s data centers, along with the Nordic countries and Dublin. All have temperate climates.

What of those who said, “Our PUE is over 2.19”? Although in most cases the sample size on a per-region basis was too small to be significant, it was nevertheless noteworthy that in the Asia-Pacific region, more than one in 10 reported a PUE greater than 2.19.

When Uptime asked respondents for PUE information, there were several answer options not addressed above (e.g., don’t operate a data center, data center is filling/emptying, don’t know). Interestingly, one in six respondents (of a survey of operators/owners/managers) didn’t know the average PUE of their largest data center. European respondents were twice as likely to know as US/Canadian respondents: for many, a good PUE figure is a badge of honor. A poor one requires an explanation.


The full report Uptime Institute global data center survey 2020 is available to members of the Uptime Institute Network here.

Share this:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on LinkedIn (Opens in new window) LinkedIn
  • Share on Reddit (Opens in new window) Reddit
  • Share on WhatsApp (Opens in new window) WhatsApp
  • Email a link to a friend (Opens in new window) Email
https://journal.uptimeinstitute.com/wp-content/uploads/2020/08/energy-Efficiency2.jpg 870 2500 Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Andy Lawrence, Executive Director of Research, Uptime Institute, alawrence@uptimeinstitute.com2020-08-24 06:00:242025-10-30 14:13:25Which regions have the most energy efficient data centers?

Content Categories

  • Journal Home
  • Executive
  • Operations
  • Design

Subscribe to Journal via Email

Enter your email address to subscribe to Uptime Institute Journal and receive notifications of new articles by email.

  • Recent

Tags

Accredited Tier Designer (9) AI (21) artificial intelligence (16) ATD (10) Carbon Emissions (7) Climate Change (13) Cloud (22) Cloud Computing (17) Cloud Costs (15) Cloud Infrastructure (29) Cloud Migration (8) Colocation (6) cooling (9) Data Center (252) Data Center Availability (40) Data Center Cooling (13) Data Center Design (45) Data Center Disaster Recovery (7) Data Center Energy Efficiency (34) Data Center Facilities Management (43) Data Center Operations (66) data center power (8) Data Center Staffing (18) DCIM (9) digital Infrastructure (117) energy (8) Energy Efficiency (38) Environmental Sustainability (18) IT (7) IT Efficiency (16) IT Outages (10) M&O (6) outages (11) Public Cloud (7) PUE (10) Regulations (24) Resiliency (9) security (7) Sustainability (34) Sustainability Reporting (7) Tier Certification (26) Tier Certification Constructed Facility (16) Uptime Institute FORCSS (6) Uptime Institute Network (13) Uptime Institute Symposium (6)
© 2014-2025 Uptime Institute, LLC All rights reserved.
  • Link to X
  • Link to LinkedIn
  • Link to Mail
Link to: Humidity and COVID-19 in data centers Link to: Humidity and COVID-19 in data centers Humidity and COVID-19 in data centers Link to: Data center workforce diversity makes good business sense Link to: Data center workforce diversity makes good business sense 2020Data center workforce diversity makes good business sense
Scroll to top Scroll to top Scroll to top