• Link to X
  • Link to LinkedIn
  • Link to Mail
  • ABOUT UI
    • Business Partners
    • Careers
    • Contact Us
    • News & Press
    • Our Team
    • Press Releases
    • Branding Guidelines
  • CONTACT
Uptime Institute Blog
  • Journal
    • Journal Home
    • Executive
    • Operations
    • Design
  • AI Services
    • AI Infrastructure Advisory
  • Tier Certification
    • Overview
    • Design
    • Construction
    • Operations
    • Tier Gap Analysis
    • Prefabricated/Modular
    • Tier Certifications List
  • Professional Services
    • Overview
    • Infrastructure Services
    • Management and Operations Services
    • Energy and Sustainability Services
    • Consulting Services
  • Education
    • Education Framework
    • Course Calendar
    • Competency & Confidence Assessments
    • Private Education
    • Graduate Roster
  • Events
    • Industry Events
    • Leadership Events
    • Network Events
  • Network
    • Overview
    • Network Calendar
    • Network Roster
    • Request Corporate Access
    • Request Guest Access
    • Uptime Network Portal
  • Intelligence
  • Clients
    • Client Stories
  • Resources
    • Data Center Industry Surveys
    • Ebooks
    • Journal Blog
    • Product Datasheets
    • Research & Reports
    • Tier Specification Documents
    • Tools
    • Webinars
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu
Blog - Latest News
Data centers weather solar storms

Data centers weather solar storms

October 19, 2022/in Design, Executive, Operations/by Jacqueline Davis, Research Analyst, Uptime Institute, [email protected]

The US Space Weather Prediction Center (SWPC) issued multiple geomagnetic storm watches throughout August and September 2022. Geomagnetic storms occur when solar storms interact with the Earth’s atmosphere and magnetic field, risking disruption to satellites, radio communications and the power grid. The strongest predicted storm earned the agency’s rating of G3 (“strong”) on a five-level classification system of geomagnetic activity — intense enough to require voltage corrections on the grid in some regions. In comparison, an “extreme” G5 geomagnetic storm could overheat or destroy high-voltage transformers, leading to widespread and lasting power outages.

A geomagnetic storm represents one type of electromagnetic pulse (EMP) — a rapid discharge of electromagnetic energy. A geomagnetic storm, also known as a geomagnetic disturbance or geomagnetic EMP, has secondary effects on power consumers that expose data centers to risk of equipment disruption and damage. The three types of EMP (geomagnetic, nuclear, or intentional) vary in their physical characteristics, but each can endanger data centers (see the Uptime Institute report Electromagnetic pulse and its risk to data centers). However, many operators do not include any type of EMP in their risk assessments, and have not implemented protective measures.

The SWPC monitors solar events and can provide hours’ or days’ notice of events likely to impact Earth. The long-term prediction of an individual geomagnetic EMP event on Earth is not possible currently. Solar events that could cause geomagnetic EMP events occur frequently but chaotically; they are often directed away from Earth and astronomers can only predict them on the basis of probability. For example, a G5 (“extreme”) event typically reaches Earth once every 25 years. Such an event caused a nine-hour outage of the Hydro-Québec transmission system in 1989. An extreme geomagnetic EMP damaged 12 transformers in South Africa in 2003. Before the advent of today’s power grid, the 1859 Carrington Event (the most intense geomagnetic storm in history) caused sparking and fires at multiple telegraph stations.

Due to its low frequency, geomagnetic EMP acts most strongly on electrical conductors running miles in length, such as high-voltage transmission lines in the power grid. The induced current behaves similarly to direct current (DC) in a system designed for alternating current (AC). Most storms, such as those in late summer 2022, are not intense enough to cause power outages. Grid operators can compensate for the induced currents of a smaller EMP event and continue delivering power. Data centers may experience problems with power quality, however — specifically, harmonic distortion (defects in AC voltage waveforms). As power is transmitted from high-voltage lines to utility customers, it passes through a succession of transformers — each of which steps down the voltage but intensifies harmonics. Harmonics are at their greatest intensity once the power reaches the end user, in this case a data center.

Most data center uninterruptable power supply (UPS) systems are designed to accommodate some harmonics and protect downstream equipment, but geomagnetic EMP events can overwhelm these built-in protections — potentially damaging the UPS or other equipment. The effects of harmonics inside a data center can include inefficient UPS operation, UPS rectifier damage, tripped circuit breakers, overheated wiring, malfunctioning motors in mechanical equipment and, ultimately, physical damage to IT equipment.

Some grid operators are already installing protective devices to guard their infrastructure against geomagnetic EMP, sparing their customers the secondary effects of outages and harmonics.

Those data center operators that include EMP risk as part of an overall risk assessment can improve their infrastructure resiliency by implementing their own EMP safeguards. The primary threats to individual data centers from geomagnetic EMP —power outages and harmonics — act via the power grid. Operators can manage this risk by disconnecting from the grid and operating on backup power. Increased on-site fuel / energy storage may be appropriate in preparing for smaller geomagnetic storms.

In the event of a large geomagnetic storm, the entire population of the affected area will be competing for fuel and other supplies and prolonged power outages are likely to outlast data centers’ fuel-storage capacity. These same conditions are likely to affect users of those applications running in a data center, leaving them unable to connect. Relying on geographically dispersed multisite resiliency (stretching over thousands of miles) is likely to offer more effective protection. More localized EMP effects — from, for example, a small geomagnetic EMP or an intentional EMP — will not affect more distant locations, so there may be a stronger economic argument for maintaining availability through such events.

Awareness of EMP as a risk to data centers is increasing. Best practice in EMP protection is not well established in the data center industry yet, but periodic risk assessments will enable operators to incorporate updated information and guidelines as these become available.

Share this:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on LinkedIn (Opens in new window) LinkedIn
  • Share on Reddit (Opens in new window) Reddit
  • Share on WhatsApp (Opens in new window) WhatsApp
  • Email a link to a friend (Opens in new window) Email
Tags: Data Center, Data Center Infrastructure, Data Center Risk, Electromagnetic Pulse, Resiliency, Solar Storms, Uninterruptible Power Supply, UPS Systems
https://journal.uptimeinstitute.com/wp-content/uploads/2022/10/Solar-Storms-featured.jpg 628 1200 Jacqueline Davis, Research Analyst, Uptime Institute, [email protected] https://journal.uptimeinstitute.com/wp-content/uploads/2022/12/uptime-institute-logo-r_240x88_v2023-with-space.png Jacqueline Davis, Research Analyst, Uptime Institute, [email protected]2022-10-19 08:00:002022-10-05 16:14:07Data centers weather solar storms
You might also like
Documenting Underfloor Conditions in an Operational Data Center
Use tools to control cloud costs before it’s too late Use tools to control cloud costs before it’s too late
Understanding how server power management works Understanding how server power management works
Data center operators will face more grid disturbances Data center operators will face more grid disturbances
AI in the Data Center2019 Data center AI: Start with the end in mind
Why are governments investigating cloud competitiveness? Why are governments investigating cloud competitiveness?
data-center-personnel Resolving the Data Center Staffing Shortage
Retail vs wholesale: finding the right colo pricing model Retail vs wholesale: finding the right colo pricing model

Content Categories

  • Journal Home
  • Executive
  • Operations
  • Design

Subscribe to Journal via Email

Enter your email address to subscribe to Uptime Institute Journal and receive notifications of new articles by email.

  • Recent

Tags

Accredited Tier Designer (9) AI (24) artificial intelligence (19) ATD (10) Carbon Emissions (7) Climate Change (13) Cloud (23) Cloud Computing (17) Cloud Costs (15) Cloud Infrastructure (29) Cloud Migration (8) Colocation (7) cooling (13) Data Center (261) Data Center Availability (40) Data Center Cooling (13) Data Center Design (45) Data Center Disaster Recovery (7) Data Center Energy Efficiency (34) Data Center Facilities Management (43) Data Center Operations (67) data center power (9) Data Center Staffing (19) DCIM (9) digital Infrastructure (126) energy (8) Energy Efficiency (38) Environmental Sustainability (18) IT (7) IT Efficiency (17) IT Outages (10) M&O (6) outages (12) Public Cloud (7) PUE (10) Regulations (25) Resiliency (9) security (7) Sustainability (34) Sustainability Reporting (7) Tier Certification (26) Tier Certification Constructed Facility (16) Uptime Institute FORCSS (6) Uptime Institute Network (13) Uptime Institute Symposium (6)
© 2014-2025 Uptime Institute, LLC All rights reserved.
  • Link to X
  • Link to LinkedIn
  • Link to Mail
Link to: Sacrifice speed to cut cloud carbon and costs Link to: Sacrifice speed to cut cloud carbon and costs Sacrifice speed to cut cloud carbon and costsSacrifice speed to cut cloud carbon and costs Link to: This Halloween, beware the vampire server Link to: This Halloween, beware the vampire server This Halloween, beware the vampire serverThis Halloween, beware the vampire server
Scroll to top Scroll to top Scroll to top